ABB ACH550-01-06A9-4+B055 [7/62] Communication set up efb

ABB ACH550-01-03A3-4+B055 [7/62] Communication set up efb
7
Communication Set-up – EFB
Communication Set-up EFB
Serial Communication Selection
To activate the serial communication, set parameter 9802
COMM PROTOCOL SEL =
•1 (
STD MODBUS).
•2 (
N2)
•3 (
FLN)
•5 (
BACNET)
Note! If you cannot see the desired selection on the panel, your drive does not have
that protocol software in the application memory.
Serial Communication Configuration
Setting 9802 automatically sets the appropriate default values in parameters that
define the communication process. These parameters and descriptions are defined
below. In particular, note that the station Id may require adjustment.
Code Description
EFB Protocol Reference
Modbus N2 FLN
5301 EFB PROTOCOL ID
Contains the identification and
program revision of the
protocol.
Do not edit. Any non-zero value entered for parameter 9802
COMM PROT SEL, sets this parameter automatically. The
format is: XXYY, where xx = protocol ID, and YY = program
revision.
5302 EFB STATION ID
Defines the node address of
the RS485 link.
Set each drive on the network with a unique value for this
parameter.
When this protocol is selected, the default value for this
parameter is: 1
Note: For a new address to take effect, the drive power
must be cycled OR 5302 must first be set to 0 before
selecting a new address. Leaving 5302 = 0 places the
RS485 channel in reset, disabling communication.
5303 EFB BAUD RATE
Defines the communication
speed of the RS485 link in
kbits per second (kbits/s).
1.2 kbits/s
2.4 kbits/s
4.8 kbits/s
9.6 kbits/s
19.2 kbits/s
38.4 kbits/s
57.6 kbits/s
76.8 kbits/s
When this protocol is selected, the default value for this
parameter is: 9.6