5-13 Terminal 29 Digital Input
Option: Function:
Select the function from the available digital
input
range and the additional options [60],
[61], [63] and [64]. Counters are used in
Smart Logic Control functions.
[0] * No operation Functions are described under parameter
group
5-1*
5-14 Terminal 32 Digital Input
Option: Function:
Select the function from the available
digital
input range and the additional
options [60], [61], [63] and [64]. Counters
are used in Smart Logic Control functions.
[39] * Day/Night
control
Functions are described under parameter
group
5-1*
5-15 Terminal 33 Digital Input
Option: Function:
Select the function from the available digital
input range and the additional options [60],
[61], [63] and [64]. Counters are used in
Smart Logic Control functions.
[0] * No operation Functions are described under parameter
group
5-1*
5-16 Terminal X30/2 Digital Input
Option: Function:
[0] * No operation This parameter is active when option module
MCB101
is installed in the frequency
converter. Functions are described under
parameter group 5-1*
5-17 Terminal X30/3 Digital Input
Option: Function:
[0] * No operation This parameter is active when option module
MCB101
is installed in the frequency
converter. Functions are described under
parameter group 5-1*
5-18 Terminal X30/4 Digital Input
Option: Function:
[0] * No operation This parameter is active when option module
MCB101
is installed in the frequency
converter. Functions are described under
parameter group 5-1*
5-19 Terminal 37 Safe Stop
Option: Function:
[1] * Safe Stop
Alarm
Coasts frequency converter when safe
stop
is activated. Manual reset from LCP,
digital input or fieldbus.
[3] Safe Stop
Warning
Coasts frequency converter when safe
stop
is activated (T-37 off). When safe
stop circuit is reestablished, the frequency
5-19 Terminal 37 Safe Stop
Option: Function:
converter will continue without manual
reset.
Choises 4 - 9 are only available when the MCB 112 PTC
Thermistor
Card is connected.
NOTE
When
Auto Reset/Warning is selected the frequency
converter opens up for automatic restart.
Overview of functions, alarms and warnings
Function No. PTC Relay
No Function [0] - -
Safe Stop Alarm [1]* - Safe Stop [A68]
Safe Stop Warning [3] - Safe Stop [W68]
PTC 1 Alarm [4] PTC 1 Safe Stop
[A71]
-
PTC 1 Warning [5] PTC 1 Safe Stop
[W71]
-
PTC 1 & Relay A [6] PTC 1 Safe Stop
[A71]
Safe Stop [A68]
PTC 1 & Relay W [7] PTC 1 Safe Stop
[W71]
Safe Stop [W68]
PTC 1 & Relay A/W [8] PTC 1 Safe Stop
[A71]
Safe Stop [W68]
PTC 1 & Relay W/A [9] PTC 1 Safe Stop
[W71]
Safe Stop [A68]
Table 3.12
W
means warning and A means alarm. For further information, see
Alarms and Warnings in section Troubleshooting in the Design Guide
or the Operating Instructions
A dangerous failure related to Safe Stop will give Alarm:
Dangerous Failure [A72].
Refer to Table 5.3 in .
3.7.3 5-3* Digital Outputs
Parameters for configuring the output functions for the
output
terminals. The 2 solid-state digital outputs are
common for terminals 27 and 29. Set the I/O function for
terminal 27 in 5-01 Terminal 27 Mode, and set the I/O
function for terminal 29 in 5-02 Terminal 29 Mode. These
parameters cannot be adjusted while the motor is running.
The digital outputs can be programmed
with
these functions:
[0] No operation
Default for all digital outputs and relay
outputs
[1] Control ready The control board receives supply voltage.
Parameter Description
VLT
®
Refrigeration Drive Programming Guide
MG16H102 - VLT
®
is a registered Danfoss trademark
63
3 3