Danfoss VLT Refrigeration Drive FC-103P37KT4 [83/203] Refrigeration drive programming guide

Danfoss VLT Refrigeration Drive FC103 FC-103P18KT2 [83/203] Refrigeration drive programming guide
8-50 Coasting Select
Option: Function:
[2] Logic AND Activates Start command via the fieldbus/serial
communication
port, AND additionally via one
of the digital inputs.
[3] * Logic OR Activates Start command via the fieldbus/serial
communication
port OR via one of the digital
inputs.
8-52 DC Brake Select
Option: Function:
Select control of the DC brake via the terminals
(digital
input) and/or via the fieldbus.
NOTE
Only selection [0] Digital input is available
when 1-10 Motor Construction is set to [1]
PM non-salient SPM.
[0] Digital
input
Activates Start command via a digital input.
[1] Bus Activates Start command via the serial
communication
port or fieldbus option.
[2] Logic AND Activates Start command via the fieldbus/serial
communication
port, AND additionally via one
of the digital inputs.
[3] * Logic OR Activates Start command via the fieldbus/serial
communication
port OR via one of the digital
inputs.
8-53 Start Select
Option: Function:
Select control of the frequency converter start
function
via the terminals (digital input) and/or
via the fieldbus.
[0] Digital
input
Activates Start command via a digital input.
[1] Bus Activates Start command via the serial
communication
port or fieldbus option.
[2] Logic AND Activates Start command via the fieldbus/serial
communication
port, AND additionally via one
of the digital inputs.
[3] * Logic OR Activates Start command via the fieldbus/serial
communication
port OR via one of the digital
inputs.
8-54 Reversing Select
Option: Function:
Select control of the frequency converter
reverse
function via the terminals (digital
input) and/or via the fieldbus.
[0] * Digital
input
Activates Reverse command via a digital input.
8-54 Reversing Select
Option: Function:
[1] Bus Activates Reverse command via the serial
communication
port or fieldbus option.
[2] Logic AND Activates Reverse command via the fieldbus/
serial
communication port, AND additionally
via one of the digital inputs.
[3] Logic OR Activates Reverse command via the fieldbus/
serial
communication port OR via one of the
digital inputs.
NOTE
This
parameter is active only when 8-01 Control Site is set
to [0] Digital and control word.
8-55 Set-up Select
Option: Function:
Select control of the frequency converter set-
up
selection via the terminals (digital input)
and/or via the fieldbus.
[0] Digital
input
Activates the set-up selection via a digital
input.
[1] Bus Activates the set-up selection via the serial
communication
port or fieldbus option.
[2] Logic AND Activates the set-up selection via the fieldbus/
serial
communication port, AND additionally
via one of the digital inputs.
[3] * Logic OR Activate the set-up selection via the fieldbus/
serial
communication port OR via one of the
digital inputs.
8-56 Preset Reference Select
Option: Function:
Select control of the frequency converter
Preset
Reference selection via the terminals
(digital input) and/or via the fieldbus.
[0] Digital
input
Activates Preset Reference selection via a
digital
input.
[1] Bus Activates Preset Reference selection via the
serial
communication port or fieldbus option.
[2] Logic AND Activates Preset Reference selection via the
fieldbus/serial
communication port, AND
additionally via one of the digital inputs.
[3] * Logic OR Activates the Preset Reference selection via the
fieldbus/serial
communication port OR via one
of the digital inputs.
Parameter Description
VLT
®
Refrigeration Drive Programming Guide
82 MG16H102 - VLT
®
is a registered Danfoss trademark
33