Danfoss MCD 100-007 4 kW [6/7] Mounting instructions

Danfoss MCD 100-011 15 kW [6/7] Mounting instructions
1.3.8 Operating at High Temperatures
Ambient temperature
Continous current
MCD 100 - 001 MCD 100 - 007 MCD 100 - 011
40°C 3 A 15 A 25 A
50°C 2.5 A* 12.5 A 20 A
60°C 2.0 A* 10 A 17 A
* Minimum 10 mm side clearance between products
Ambient temperature
Duty-cycle rating (15 min. max. on-time)
MCD 100 - 007 MCD 100 - 011
40°C 15 A (100 % duty-cycle) 25 A (100 % duty-cycle)
50°C 15 A (80 % duty-cycle) 25 A (80 % duty-cycle)
60°C 15 A (65 % duty-cycle) 25 A (65 % duty-cycle)
1.3.9 Over Heat Protection
If required the controller can be protected against
overheating by inserting a thermostat in the slot on the
right-hand side of the controller.
Order: UP 62 thermostat 037N0050
Depending on the application the thermostat can be
connected in series with the control circuit of the main
contactor. When the temperature of the heat sink exceeds
90° C the main contactor will be switched OFF. A manual
reset is necessary to restart this circuit.
For wiring connections see 1.2 Application Examples.
1.3.10 Mounting Instructions
The controller is designed for vertical mounting. If the
controller is mounted horizontally the load current must
be reduced by 50%.
The controller needs no side clearance.
Clearance between two vertical mounted controllers must
be minimum 80 mm (3.15”).
Clearance between controller and top and bottom walls
must be minimum 30 mm (1.2”).
1.4 Application Examples
1.4.1 Overheat protection
Example 1
The thermostat can be connected in series with the control
input of the soft starter. When the temperature of the heat
sink exceedes 90°C the soft starter will be switched OFF.
All about MCD 100 MCD 100 Design Guide
6 MG12A202 - VLT
®
is a registered trademark
1
1