Danfoss MCD 100-007 4 kW [7/7] Line controlled soft start

Danfoss MCD 100-011 15 kW [7/7] Line controlled soft start
NOTE
When the temperature has dropped approximately 30°C
the controller will automatically be switched On again. This
is not acceptable in some applications.
Example 2
The thermostat is connected in series with the control
circuit of the main contactor. When the temperature of the
heat sink exceeds 90°C the main contactor will be
switched OFF. This circuit requires manual reset to restart
the motor.
1.4.2 Line Controlled Soft Start
When the contractor C1 is switched to the ON-State, the
soft starter will start the motor, according to the settings
of the Ramp-up time and Initial torque adjustments.
When the contactor C1 is switched to the OFF-State, the
motor will be switched off instantaneously.
In this application the contactor will have no load during
making operation. The contactor will carry and break the
nominal motor current.
1.4.3 Input Controlled Soft Start
When the control voltage is applied to A1 - A2, the MCD
soft starter will start the motor, according to the settings
of the Ramp-up time and Initial torque adjustments.
When the control voltage is switched OFF, the motor will
be soft stopped according to the settings of the Ramp-
down time adjustments.
To switch off instantaneously set the Ramp-down time to
0.
All about MCD 100 MCD 100 Design Guide
MG12A202 - VLT
®
is a registered trademark 7
1
1