Vacon NXS0007-6A2L0SSS [4/12] Ratings and dimensions

Vacon NXS0004-6A2L0SSS [4/12] Ratings and dimensions
Function Availability
IP21 Standard
IP54 (FR10 only) Optional (H: +20mm)
Integrated fuses Standard
Integrated load switch Optional
EMC ltering L Standard
EMC ltering T Optional
Integrated brake chopper (cabling top entry) Optional (H: +122 mm)
Ratings and dimensions
Mains voltage 500-690 V, 50/60 Hz, 3~, Wall-mounted units
Mains voltage 500-690 V, 50/60 Hz, 3~, Standalone units
Hardware configurations, Standalone units
AC drive type
Loadability Motor shaft power
Enclosure
Dimensions
W x H x D [mm]
Low (+40°C) High (+50°C)
Maximum
current I
S
400 V supply
Rated
continuous
current I
L
[A]
10%
overload
current [A]
Rated
continuous
current I
H
[A]
50%
overload
current [A]
10% overl.
P [kW]
50% overl.
P [kW]
NXS 0004 6 A 2 L 0 SSS 4.5 5.0 3.2 4.8 6.4 3 2.2 FR6 195 x 519 x 237
NXS 0005 6 A 2 L 0SSS 5.5 6.1 4.5 6.8 9.0 4 3 FR6 195 x 519 x 237
NXS 0007 6 A 2 L 0 SSS 7.5 8.3 5.5 8.3 11.0 5.5 4 FR6 195 x 519 x 237
NXS 0010 6 A 2 L 0 SSS 10 11.0 7.5 11.3 15.0 7.5 5.5 FR6 195 x 519 x 237
NXS 0013 6 A 2 L 0 SSS 13.5 14.9 10 15.0 20.0 11 7.5 FR6 195 x 519 x 237
NXS 0018 6 A 2 L 0 SSS 18 19.8 13.5 20.3 27 15 11 FR6 195 x 519 x 237
NXS 0022 6 A 2 L 0 SSS 22 24.2 18 27.0 36 18.5 15 FR6 195 x 519 x 237
NXS 0027 6 A 2 L 0 SSS 27 29.7 22 33.0 44 22 18.5 FR6 195 x 519 x 237
NXS 0034 6 A 2 L 0 SSS 34 37 27 41 54 30 22 FR6 195 x 519 x 237
NXS 0041 6 A 2 L 0 SSS 41 45 34 51 68 37.5 30 FR7 237 x 591 x 257
NXS 0052 6 A 2 L 0 SSS 52 57 41 62 82 45 37.5 FR7 237 x 591 x 257
NXS 0062 6 A 2 L 0 SSS 62 68 52 78 104 55 45 FR8 291 x 758 x 344
NXS 0080 6 A 2 L 0 SSS 80 88 62 93 124 75 55 FR8 291 x 758 x 344
NXS 0100 6 A 2 L 0 SSS 100 110 80 120 160 90 75 FR8 291 x 758 x 344
NXS 0125 6 A 2 L 0 SSF 125 138 100 150 200 110 90 FR9 480 x 1150 x 362
NXS 0144 6 A 2 L 0 SSF 144 158 125 188 213 132 110 FR9 480 x 1150 x 362
NXS 0170 6 A 2 L 0 SSF 170 187 144 216 245 160 132 FR9 480 x 1150 x 362
NXS 0208 6 A 2 L 0 SSF 208 229 170 255 289 200 160 FR9 480 x 1150 x 362
AC drive type
Loadability Motor shaft power
Enclosure
Dimensions
W x H x D [mm]
Low (+40°C) High (+40°C)
Maximum
current I
S
690 V supply
Rated
continuous
current I
L
[A]
10%
overload
current [A]
Rated
continuous
current I
H
[A]
50%
overload
current [A]
10% overl.
P [kW]
50% overl.
P [kW]
NXS 0261 6 A 2 L 0 SSA 261 287 208 312 375 250 200 FR10 595 x 2018 x 602
NXS 0325 6 A 2 L 0 SSA 325 358 261 392 470 315 250 FR10 595 x 2018 x 602
NXS 0385 6 A 2 L 0 SSA 385 424 325 488 585 355 315 FR10 595 x 2018 x 602
NXS 0416 6 A 2 L 0 SSA* 416 458 325 488 585 400 315 FR10 595 x 2018 x 602
NXS 0460 6 A 2 L 0 SSA 460 506 385 578 693 450 355 FR11 794 x 2018 x 602
NXS 0502 6 A 2 L 0 SSA 502 552 460 690 828 500 450 FR11 794 x 2018 x 602
NXS 0590 6 A 2 L 0 SSA* 590 649 502 753 904 560 500 FR11 794 x 2018 x 602
For all VACON® NXS drives, overloadability is dened as follows:
High: 1.5 x I
H
(1 min/10 min) @ 50°C; Low: 1.1 x I
L
(1 min/10 min) @ 40°C; I
S
for 2 sec every 20 sec.
* Max. ambient temperature of +35˚C
4 Danfoss Drives · DKDD.PB.913.A1.02