23
Riotec / Riotec Z
4.4 Important points on the operation of the
pump, PLR and Tele-Monitor
Indicating errors (menu 10) and the acknowledge-
ment of errors has top priority. What this means is that
errors take precedence on the pump’s display and
that they must be acknowledged and removed.
Should setting alterations be made to the Riotec
module or from the Tele-Monitor and not be confirmed
by pressing the button, the setting returns to the pre-
vious setting 30 s after the last entry has been made.
– Pump
↔
PLR: Upon receiving a command from
the PLR, the pump automatically switches over to
PLR mode. . appears on the display. The
pump is now blocked and cannot be operated.
Exception , , Optimisation, acknow-
ledgement of errors. In the case of pumps with
P
1
< 500 W (see rating plate) only error acknowled-
gement is possible.
– Pump
↔
Tele-Monitor without Key function: The
last command, whether from the Tele-Monitor or
the Riotec module is carried out by the pump.
– Pump
↔
Tele-Monitor with Key function: On
receiving the command “Key function on”, the
current Riotec module settings remain as they are.
appears in the display. The pump can no longer
be operated except to acknowledge errors.
– Pump
↔
PLR
↔
Tele-Monitor: With this configu-
ration the pump gives the settings on the PLR prior-
ity. The PLR settings can be interrupted by the Tele-
Monitor. Settings can now be made via the Tele-
Monitor or to the Riotec module. The connection to
the MPC is re-established 5 min after the last set-
ting made via the Tele-Monitor. disappears
from the display for the length of the interruption.
4.5 Products delivered
– Complete pump
– Two-piece heat insulation unit, single pump on
– Installation and Operating Instructions
4.6 Accessories
– IF-module for connection to PLR/interface con-
verter or a second Riotec. For a Riotec Z or two
single Riotecs two IF-modules are necessary for
the automatic control of the double pump functions.
– Tele-Monitor.
5. Installation
5.1 Assembly
– The pump must be installed in a dry, well-aired,
frost-free room.
– Prior to installation of the single pump the two shells
are to be removed from the thermal lagging.
– Before installing the pump, make sure that all weld-
ing and soldering on the pipe system has been
completed and that the pipe system has been
flushed out if necessary. Dirt can have an adverse
effect on the functioning of the pump.
– The pump must be installed in an easily accessible
place to allow for maintenance even after assembly.
– It is recommended that a shut-off device be installed
in front of and behind the pump. This avoids the
necessity to empty and fill the unit every time a
pump has to be replaced. Assembly is to be carried
out in such a way that no drops fall onto the pump
motor or the terminal box.
– When installing flow pipes in open units, the expan-
sion flow pipe must branch off before the pump.
– Assembly should be voltage-free. The pipes must
be attached in such a way that the pump does not
bear the weight of the pipes.
– The direction of flow must correspond to the arrow
on the pump housing.
– The air inlet to the heat sink must not be blocked in
any way.
– Only installation positions in accordance with Fig
7a/7b are permissible. The pump shaft must lie
horizontally. For pumps with P
1
≥ 500 W the ribs of
the heat sink must stand vertically to the electronic
module. It is possible that the motor housing has to
be turned after loosening the Allen screws.
In doing so, care must be taken not
to damage the O-ring between the
split pot and the pump housing. The
O-ring must lie, unturned, in the
edge of the split pot which faces the
impeller.
– Place both thermal lagging shells on the single
pump and press them together so that the pilot pins
lock into their respective, opposite holes.
– For units which are to be insulated,
only the pump housing may be in-
sulated. The condensation water
holes on the motor flange must
remain open.
ATTENTION!
ATTENTION!
Содержание
- Riotec riotec z 1
- Plr modul 2
- Riotec riotec z 2
- Riotec riotec z 3
- Fig 7a 4
- Fig 7b 4
- Riotec riotec z 4
- Riotec riotec z 5
- General information 8
- Riotec riotec z 8
- Safety 8
- Description of product and accessories 9
- Riotec riotec z 9
- Transport and storage 9
- Riotec riotec z 10
- Riotec riotec z 11
- Riotec riotec z 12
- Riotec riotec z 13
- Riotec riotec z 14
- Installation 15
- Riotec riotec z 15
- Operation 16
- Riotec riotec z 16
- Problems causes and solutions 17
- Riotec riotec z 17
- Service 17
- Fourth column means that the error reading has to be reset manually at the pump fifth column switch off at x errors 24 hrs x 1 in the event of a serious error the unit imme diately switches off when the error first arises x 6 an error arises the pump switches off once the error has been rectified the pump switches on again when the same error arises for the sixth time within the space of 24 hours the 18
- Pump switches off permanently and registers ssm manual reset is necessary 18
- Riotec riotec z 18
- Tabelle i part 8 problems causes and solutions 18
- W the error w arning only appears on the display but the error led does not light up the pump continues to run the error can occur an infinite number of times the indicated operating condition should not be ignored for long periods of time the cause of the error must be removed 18
- If the fault cannot be remedied please contact your local plumbing and heating specialist or ksb customer services 19
- In the event of high temperatures and high system pressure the pumps should be allowed to cool down danger of liquid boiling over 19
- Riotec riotec z 19
- Subject to technical alterations 19
Похожие устройства
- KSB Riotec 50-60 Инструкция по эксплуатации
- KSB Riotec 50-60 Технические данные
- KSB Riotec 50-70 Инструкция по эксплуатации
- KSB Riotec 50-70 Технические данные
- KSB Riotec 50-100 Инструкция по эксплуатации
- KSB Riotec 50-100 Технические данные
- KSB Riotec 65-100 Инструкция по эксплуатации
- KSB Riotec 65-100 Технические данные
- KSB Riotec 80-100 Инструкция по эксплуатации
- KSB Riotec 80-100 Технические данные
- KSB Riotec 100-100 Инструкция по эксплуатации
- KSB Riotec 100-100 Технические данные
- KSB Riotec Z 25-70 Инструкция по эксплуатации
- KSB Riotec Z 25-70 Технические данные
- KSB Riotec Z 30-70 Инструкция по эксплуатации
- KSB Riotec Z 30-70 Технические данные
- KSB Riotec Z 32-70 Инструкция по эксплуатации
- KSB Riotec Z 32-70 Технические данные
- KSB Riotec Z 30-100 Инструкция по эксплуатации
- KSB Riotec Z 30-100 Технические данные