KSB Riotec 40-100 [8/19] General information
![KSB Riotec 50-70 [8/19] General information](/views2/1579208/page8/bg8.png)
16
Riotec / Riotec Z
1. General Information
Assembly and installation should only be
carried out by qualified personnel!
1.1 Uses
The circulating pump is used to transport liquids in
warm water heating systems.
Under no circumstances may the pump come in
contact with drinking water or foodstuffs.
1.2 Product data
1.2.1 Key
Riotec (Z) 40-100
Heating circulating pumps
Double pump
Width of flange in mm
Max. head in m
m x 10 (100 =10 m)
1.2.2 Connection and output data
– Flow media:
– Heating water acc. to VDI 2035.
– Water glycol mixtures containing up to 50 % gly-
col. Should glycol be added to the liquid, the flow
data must be adapted to correspond to the
higher viscosity. Only brand products with anti-
corrosion inhibitors should be used. The manu-
facturer’s instructions must always be strictly
adhered to.
– If another medium is to be used, it must be
cleared by KSB.
– Temperature range of the flow medium: +20 °C to
+110°C.
– Max. ambient temperature: 40 °C.
– In order to avoid the build up of condensation water,
the temperature of the room must be lower the
temperature of the flow medium.
– Max. operating pressure of the pump: see rating
plate.
– Min. supply height at the air intake in order to avoid
cavity noises (at max. water temperature T
max
):
T
max
R 1 R 11/4 DN 40 DN 50 DN 65 DN 80
1+50°C 0.05 bar 0.3 bar
1+95°C 0.5 bar 1.0 bar
+110°C 1.1 bar 1.6 bar
These values are valid up to a height of 300 m
above sea level. For situations above this height
add 0.01 bar for every additional 100 m.
– system of protection IP 43.
– Connection to 1~230 V, 50 Hz in accordance with
IEC 38.
– When ordering spare parts, please give all the infor-
mation on the pump/motor rating plate.
2. Safety
These instructions contain important information which
must be followed when installing and operating the
pump. It is therefore imperative that they be read by
both the installer and the operator before the pump is
installed or started up.
Both the general safety points in this section and the
more specific safety points in the following sections
should be noted.
2.1 Instruction symbols in this operating manual
Safety precautions in these operating instructions
which, if not followed, could cause personal injury are
indicated by the symbol:
Safety precautions warning of danger due to electri-
city are indicated by the symbol
The following symbol is used to indicate that by ignor-
ing the relevant safety instructions, damage could be
caused to the pump/machinery and its functions:
2.2 Staff training
The personnel installing the pump must have the
appropriate qualifications for this work.
2.3 Risks incurred by failure to comply with
the safety precautions
Failure to comply with the safety precautions could
result in personal injury or damage to the pump or
installation. Failure to comply with the safety precau-
tions could also invalidate any claim for damages.
ATTENTION!
Содержание
- Riotec riotec z 1
- Plr modul 2
- Riotec riotec z 2
- Riotec riotec z 3
- Fig 7a 4
- Fig 7b 4
- Riotec riotec z 4
- Riotec riotec z 5
- General information 8
- Riotec riotec z 8
- Safety 8
- Description of product and accessories 9
- Riotec riotec z 9
- Transport and storage 9
- Riotec riotec z 10
- Riotec riotec z 11
- Riotec riotec z 12
- Riotec riotec z 13
- Riotec riotec z 14
- Installation 15
- Riotec riotec z 15
- Operation 16
- Riotec riotec z 16
- Problems causes and solutions 17
- Riotec riotec z 17
- Service 17
- Fourth column means that the error reading has to be reset manually at the pump fifth column switch off at x errors 24 hrs x 1 in the event of a serious error the unit imme diately switches off when the error first arises x 6 an error arises the pump switches off once the error has been rectified the pump switches on again when the same error arises for the sixth time within the space of 24 hours the 18
- Pump switches off permanently and registers ssm manual reset is necessary 18
- Riotec riotec z 18
- Tabelle i part 8 problems causes and solutions 18
- W the error w arning only appears on the display but the error led does not light up the pump continues to run the error can occur an infinite number of times the indicated operating condition should not be ignored for long periods of time the cause of the error must be removed 18
- If the fault cannot be remedied please contact your local plumbing and heating specialist or ksb customer services 19
- In the event of high temperatures and high system pressure the pumps should be allowed to cool down danger of liquid boiling over 19
- Riotec riotec z 19
- Subject to technical alterations 19
Похожие устройства
- KSB Riotec 50-60 Инструкция по эксплуатации
- KSB Riotec 50-60 Технические данные
- KSB Riotec 50-70 Инструкция по эксплуатации
- KSB Riotec 50-70 Технические данные
- KSB Riotec 50-100 Инструкция по эксплуатации
- KSB Riotec 50-100 Технические данные
- KSB Riotec 65-100 Инструкция по эксплуатации
- KSB Riotec 65-100 Технические данные
- KSB Riotec 80-100 Инструкция по эксплуатации
- KSB Riotec 80-100 Технические данные
- KSB Riotec 100-100 Инструкция по эксплуатации
- KSB Riotec 100-100 Технические данные
- KSB Riotec Z 25-70 Инструкция по эксплуатации
- KSB Riotec Z 25-70 Технические данные
- KSB Riotec Z 30-70 Инструкция по эксплуатации
- KSB Riotec Z 30-70 Технические данные
- KSB Riotec Z 32-70 Инструкция по эксплуатации
- KSB Riotec Z 32-70 Технические данные
- KSB Riotec Z 30-100 Инструкция по эксплуатации
- KSB Riotec Z 30-100 Технические данные