CHV190 series special inverter for crane
- 151 -
The data addresses of each function parameters. Please refer to the sixth column of
APPENDIX E.
The data address of control and status parameters please refer to the following table.
Parameter
description
Address
Meaning of value
R/W
feature
0001H: Up
0002H: Down
0003H: JOG forward
0004H: JOG reverse
0005H: Stop
0006H: Coast to stop
0007H: Reset fault
Control
command
1000H
0008H: JOG stop
W/R
0001H: Forward running
0002H: Reverse running
0003H: Standby
Inverter status 1001H
0004H: Fault
R
Frequency
source
communication
setting
2000H
Communication Setting Range
(-10000~10000)
Note: the communication setting is
the percentage of the relative value
(-100.00%~100.00%). If it is set as
frequency source, the value is the
percentage of the maximum
frequency (P0.04). If it is set as PID
(preset value or feedback value), the
value is the percentage of the PID.
W/R
Virtual terminal
input function
setting
2001H
Setting range: 000H~03FFH. Each bit
corresponds to S1~S10, HDI1, HDI2
and S6~S8 respectively.
Notice: The functional code P5.01
should be set to the communication
virtual terminal input function, and
should also be unrelated to HDI1 and
HDI2 input types.
W/R