6.4. Using the REV/0/FWD selector switch (Switched version only)
By adjusting the parameter settings the Optidrive can be configured for multiple applications and not just for Forward or Reverse.
This could typically be for Hand/Off/Auto applications (also known and Local/Remote) for HVAC and pumping industries.
Switch Position
Parameters to
Set
Notes
P-12
Run Reverse
STOP
Run Forward
0
Factory Default Configuration
Run Forward or Reverse with speed controlled
from the Local POT
STOP
STOP
Run Forward
0
Run forward with speed controlled form the
local POT
Run Reverse - disabled
Preset Speed 1
STOP
Run Forward
0
Run Forward with speed controlled from the
Local POT
Preset Speed 1 provides a „Jog‟ Speed set in
P-20
Run Reverse
STOP
Run Forward
0
Run Forward or Reverse with speed controlled
from the Local POT
Run in Auto
STOP
Run in Hand
0
Run in Hand Speed controlled from the Local
POT
Run in Auto 0 Speed controlled using Analog
input 2 e.g. from PLC with 4-20mA signal.
Run in Speed
Control
STOP
Run in PI Control
5
In Speed Control the speed is controlled from
the Local POT
In PI Control, Local POT controls PI set point
Run in Preset
Speed Control
STOP
Run in PI Control
5
In Preset Speed Control, P-20 sets the Preset
Speed
In PI Control, POT can control the PI set point
(P-44=1)
Run in Hand
STOP
Run in Auto
3
Hand speed controlled from the Local POT
Auto Speed Reference from Modbus
Run in Hand
STOP
Run in Auto
3
Hand Speed reference from Preset Speed 1
(P-20)
Auto Speed Reference from Modbus
NOTE
To be able to adjust parameter P-15, extended menu access must be set in P-14 (default value is 101)