Invertek Drives ODE-2-14150-3KA1 [20/24] Keypad mode p 12 1 or 2

Invertek Drives ODE-2-12150-1KB1 [20/24] Keypad mode p 12 1 or 2
20 Optidrive E2 IP66 / NEMA 4X User Guide
www.invertek.co.uk
Analog speed input with 1 preset speed
and motor thermistor trip
Local or remote analog speeds
(2 analog inputs)
Push button fwd/rev/stop with fast stop
using 2
nd
deceleration ramp
8.2. Keypad mode (P-12 = 1 or 2)
P-15
Digital input 1 (T2)
Digital input 2 (T3)
Digital input 3 (T4)
Analog input (T6)
Comments
0, 1,
5,
8..12
Open: Stop (disable)
Closed: Run (enable)
Closed : remote UP
push-button
Closed : remote DOWN
push-button
Open : Forward
+24V : Reverse
2
Open: Stop (disable)
Closed: Run (enable)
Closed : remote UP
push-button
Closed : remote DOWN
push-button
Open : Keypad speed ref
+24V : Preset speed 1
3
1)
Open: Stop (disable)
Closed: Run (enable)
Closed : remote UP
push-button
External trip input :
Open: Trip, Closed: Run
Closed : remote DOWN
push-button
Connect external PTC
motor thermistor or similar
to digital input 3
4
Open: Stop (disable)
Closed: Run (enable)
Closed : remote UP
push-button
Open : Keypad speed ref
Closed : Analog input 1
Analog input 1
6
1)
Open: Stop (disable)
Closed: Run (enable)
Open : Forward run
Closed : Reverse run
External trip input :
Open: Trip, Closed: Run
Open : Keypad speed ref
+24V : Preset speed 1
Connect external PTC
motor thermistor or similar
to digital input 3
7
Open: Forward Stop
Closed: Forward Run
Open: Reverse Stop
Closed: Reverse Run
External trip input :
Open: Trip, Closed: Run
Open : Keypad speed ref
+24V : Preset speed 1
Closing digital inputs 1 and
2 together carries out a
fast stop (P-24)
Example Wiring
Remote push button speed control with
fwd/rev