3. Mechanical Installation
3.1. General
Store the Optidrive in its box until required. Storage should be clean and dry and within the temperature range 40°C to +60°C
Install the Optidrive on a flat, vertical, flame-resistant, vibration-free mounting. If higher IP/NEMA ratings are required mount
within a suitable enclosure, according to EN60529.
Mount the drive vertically and do not restrict the air flow to the heat sink fins. • The drive generates heat. Allow sufficient space
around the unit for heat dissipation. Do not mount the drive near heat-radiating elements or in direct sunlight
The Optidrive must be installed in a pollution degree 1 or 2 environment
The IP66/NEMA 4X drive is intended for INDOOR USE ONLY
Ensure that all terminals are tightened to the appropriate torque setting.
Avoid Condensation built up in the drive. The washdown process of the drive may create a temperature and humidity change
in and around the drive. If the unit is mounted in a cool environment and washed down with higher temperature water, as the
drive cools to room temperature, condensation can form inside the drive, especially around the display. To prevent this from
happening, avoid using sealed connectors around rubber-coated cables to seal the drive. These do not allow any air transfer
and hence create a level of condensation and humidity that exceeds the drive‟s rating.
3.2. Mechanical dimensions and mounting
Drive
Size
A
B
D
E
F
G
H
I
J
mm
in
mm
in
in
mm
in
mm
mm
in
mm
mm
in
mm
in
1
232.0
9.13
207.0
8.15
7.44
25.0
0.98
179.0
161.0
6.34
148.5
4.0
0.16
8.0
0.31
2
257.0
10.12
220.0
8.67
7.87
28.5
1.12
186.5
188.0
7.40
176.0
4.2
0.17
8.5
0.33
3
310.0
12.20
276.5
10.89
9.90
33.4
1.31
228.7
210.5
8.29
197.5
4.2
0.17
8.5
0.33
Control Terminal Torque Settings of 0.5 Nm (4.5 lb-in)
Power Terminal Torque Settings of 1 Nm (9 lb-in)
The IP66/NEMA 4X Optidrives can be installed side-by-side
with their heatsink flanges touching. This gives adequate
ventilation space between drives. If the Optidrive is to be
installed above another drive or any other heat-producing
device, the minimum vertical spacing is 150mm (5.9 inches)
above and below. Mount the drive vertically and do not restrict
the air flow to the heat sink fins.