Fluid handled
Application limit
Temperature
Materials
casing/impeller
Shaft seal
mechanical seal
Comments
Grey cast iron/
grey cast iron
Grey cast iron/
stainless steel
Grey cast iron/
bronze
U3BEGG (WE 25, 35)
AQ1EGG (WE 55)
Q1Q1EGG
U3U3VGG
Q1Q1X4GG
BQ1EGG
[°C] G GC GB 6 22 7 9 10 11
Heating water
2)
≤ 110
If used as a circulating pump to DIN 4752: p maximum
≤ 10 bar
Heating water ≤ 140
Heating water ≥ 110
Condensate ≤ 110
Cooling water
(without antifreeze)
≤ 60
Open circuit: GB 10 required
Cooling water pH ≥ 7.5
(with antifreeze
3)
)
≥ -30
≤ 60
Open loop: use GB
Cooling water pH ≥ 7.5
(with antifreeze
3)
)
≥ 60
≤ 110
Open loop: use GB
Slightly contaminated water ≤ 60
Pure water
4)
≤ 60
Raw water ≤ 60
Swimming pool water (fresh
water)
≤ 60
Also applies to requirements as per DIN 19643
Swimming pool water
5)
:
filtration
≤ 40
Variant GB
Shaft C45+N, shaft sleeve CrNiMo steel,
nut A4/AISI 316, key A2,
casing wear ring (suction and discharge side) grey cast
iron JL 1040/ CI
Swimming pool water
5)
: water
features; without turbulences
and/or air content
≤ 40
Variant GB
Shaft C45+N, shaft sleeve CrNiMo steel,
nut A4/ AISI 316, key A2,
casing wear ring (suction and discharge side) CC495K-
GS
Dam water ≤ 60
If solids are contained, contact KSB.
Drinking water
6)
≤ 60
Partly desalinated water ≤ 120
Fully desalinated water as boiler
feed water
≤ 110
Refrigerants, cooling brines
Cooling brine; inorganic,
pH value > 7.5, inhibited
≥ -30
≤ 25
Water with antifreeze, pH value
≥ 7.5
≥ -30
≤ 60
Water with antifreeze, pH value
≥ 7.5
≥ 60
≤ 110
Oils/emulsions
Drilling/grinding emulsion ≤ 60
Oil-water emulsion ≤ 60
Etaline-R
Table of fluids handled and associated material combinations
= standard
Fluid handled Application limits Casing/impeller
materials
Mechanical seal
material
Design variant code,
mechanical seal
G M S 4
Water
Service water t ≤ 60 °C; p ≤ 16 bar
G4
Fire-fighting water
7)
t ≤ 60 °C; p ≤ 16 bar
M4
2)
Treatment to VdTÜV 1466; additional requirement: O2 < 0.02 mg/l
3)
Antifreeze on ethylene glycol basis with inhibitors Content: >20 % to 50 % (e.g. Antifrogen N)
4)
No ultra-pure water! Conductivity at 25 °C: ≤ 800 μS/cm, neutral with regard to chemical corrosion
5)
For France, observe the applicable rules as per ministerial order dated 18 January 2002.
6)
For France, ACS approval is required.
Heating / Air-conditioning / Ventilation
In-line Pumps
Etaline / Etaline-R
7