KSB Etaline ETL-125-125-160 160L [8/90] Etaline etaline r

KSB Etaline ETL-100-100-250 180M [8/90] Etaline etaline r
Fluid handled Application limits Casing/impeller
materials
Mechanical seal
material
Design variant code,
mechanical seal
G M S 4
Heating water
8)
t ≤ 120 °C; p ≤16 bar
G4
Heating water
8)
t ≤ 140 °C; p ≤ 25 bar
S4
Heating water
8)
t ≤ 110 °C; p ≤ 16 bar
G4
Condensate
8)
t ≤ 120 °C; p ≤ 16 bar
Contact KSB.
Cooling water
7)
(without
antifreeze)
t ≤ 60 °C; p ≤ 16 bar
G4
Cooling water pH ≥ 7.5 (with
antifreeze)
9)
t ≥ -30 °C; p ≤ 16 bar
t ≤ 110 °C; p ≤ 25 bar
G4
Slightly contaminated water
7)
t ≤ 60 °C; p ≤ 16 bar
G4
Pure water
10)
t ≤ 25 °C; p ≤ 16 bar
G4
Raw water (irrigation)
7)
t ≤ 60 °C; p ≤ 16 bar
G4
Raw water (industrial application)
7)
t ≤ 60 °C; p ≤ 16 bar
G4
Swimming pool water (fresh
water)
7)
t ≤ 60 °C; p ≤ 16 bar
G4
Dam water
7)
t ≤ 60 °C; p ≤ 16 bar
M4
Drinking water
7)
t ≤ 60 °C; p ≤ 16 bar
M4
Partly desalinated water
8)
t ≤ 120 °C; p ≤ 16 bar
Contact KSB.
Fully desalinated water as boiler
feed water
8)
t ≤ 120 °C; p ≤ 16 bar
G4
Refrigerants, cooling brines
Cooling brine, inorganic, pH ≥ 7.5,
inhibited
t ≥ -30 °C; p ≤ 16 bar
t ≤ 25 °C
G4
Water with antifreeze pH ≥ 7.5
7)9)
t ≥ -30 °C; p ≤ 16 bar
t ≤ 110 °C
G4
Oils/emulsions
Diesel oil, extra light fuel oil t ≤ 60 °C; p ≤ 16 bar
S4
Lubricating oil, turbine oil, does
not apply to SF-D oils (hardly
flammable)
t ≤ 80 °C; p ≤ 16 bar
S4
Drilling/grinding emulsion t ≤ 60 °C; p ≤ 16 bar
G4
Oil-water emulsion t ≤ 60 °C; p ≤ 16 bar
G4
Cleaning agents
Lyes for bottle rinsers t ≤ 90 °C; p ≤ 16 bar
Brewery applications
Beer mash t ≤ 100 °C; p ≤ 16 bar
G4
Beer wort t ≤ 100 °C; p ≤ 16 bar
G4
Pressure and temperature limits
Pressure and temperature limits of the pump
Pressure and temperature limits of the pump
Material variant Fluid temperature
[°C]
11)12)
Test pressure
[bar]
13)
Etaline
G, GC,GB -30 to +140 Up to 21
Etaline-R
7)
General evaluation criteria for results of water analysis; pH value ≥ 7; chlorides content (Cl) ≤ 250 mg/kg. Chlorine
(Cl2) ≤ 0.6 mg/kg
8)
Treatment to VdTÜV 1466; additional requirement: O2 < 0.02 mg/l
9)
Antifreeze on ethylene glycol basis with inhibitors Content: > 20 % to 50 % (e.g. Antifrogen N)
10)
No ultra-pure water! Conductivity at 25 °C: < 800 μS/cm, neutral with regard to chemical corrosion
11)
For hot water heating systems to DIN 4752, Section 4.5, application limits must be observed.
12)
For fluid temperatures >140 °C use Etanorm SYT.
13)
The casing components are checked for leakage by means of internal pressure tests to AN 1897/75-03D00 with water.
Heating / Air-conditioning / Ventilation