4.5 Auto-Tuning
YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual 103
Start-Up Programming
& Operation
4
T1-09: Motor No-Load Current
Sets the no-load current for the motor. The default setting displayed is no-load current automatically calculated from the
output power set in T1-02 and the motor rated current set to T1-04. Enter the data listed on the motor test report. Leave
this data at the default setting if the motor test report is not available.
T1-10: Motor Rated Slip
Sets the rated slip for the motor.
The default setting displayed is the motor rated slip for a Yaskawa motor calculated from the output power set in T1-02.
Enter the data listed on the motor test report.
Parameter Settings during PM Motor Auto-Tuning: T2
The T2- parameters are used to set the Auto-Tuning input data for PM motor tuning.
T2-01: PM Auto-Tuning Mode Selection
Selects the type of Auto-Tuning to be performed. Refer to Auto-Tuning for Permanent Magnet Motors on page 96 for
details on different types of Auto-Tuning.
0: Motor Data Input
1: PM Stationary Auto-Tuning
2: PM Stationary Stator Resistance Auto-Tuning
3: Initial Magnet Pole Search Parameters Auto-Tuning
4: Stationary PG Encoder Offset Auto-Tuning
10: Rotational PG Encoder Offset Auto-Tuning
11: Rotational Back EMF Constant Auto-Tuning
T2-04: PM Motor Rated Power
Specifies the PM motor rated power in kilowatts.
T2-05: PM Motor Rated Voltage
Sets the PM motor rated voltage.
T2-06: PM Motor Rated Current
Enter the PM motor rated current in amps.
No.
<1> The value will have two decimal places (0.01 A) in the drive models 2A0018 to 0033 and 4A0009 to 0018 (refer to Table A.1 and Table A.2),
and one decimal place (0.1 A) in the drive models 2A0047 to 0415 and 4A0024 to 0216
Name Setting Range Default
T1-09 <1> Motor No-Load Current
0 to [T1-04] A
Max: 0 to 2999.9)
No. Name Setting Range Default
T1-10 Motor Rated Slip 0.00 to 20.00 Hz
No. Name Setting Range Default
T2-01 PM Auto-Tuning Mode Selection 0 to 4, 10, 11 0
No. Name Setting Range Default
T2-04 PM Motor Rated Power 0.00 to 650.00 kW Depending on o2-04
No. Name Setting Range Default
<1> Values shown are specific to 200 V class drives. Double value for 400 V class drives.
T2-05 PM Motor Rated Voltage 0.0 to 255.0 V <1> 200.0 V <1>
No. Name Setting Range Default
T2-06 PM Motor Rated Current
10% to 200% of the drive rated cur-
rent.
Depending on o2-04