5.7 H: Terminal Functions
YASKAWA ELECTRIC SIEP C710616 33D YASKAWA AC Drive L1000A Technical Manual 181
Parameter Details
5
Setting 1A: During down direction
A digital output set for “During down direction” will close whenever the drive is running the elevator in down direction.
Figure 5.27
Figure 5.27 Down Direction Output Example Time Chart
Setting 1B: During baseblock (N.C.)
Output opens to indicate that the drive is in a baseblock state. While Baseblock is executed, output transistors do not
switch and no main circuit voltage is output.
Setting 1C: Motor 2 selection
Indicates which motor is selected when another output terminal is set up to switch drive operation between two motors
(H1- = 16). Refer to Setting 16: Motor 2 selection on page 173 for details on switching motors.
Setting 1D: During regeneration
Terminal closes when the motor is driven in the regenerative mode.
Setting 1E: Reset enabled
An output set for “Reset enabled” closes when the drive attempts to reset after a fault has occurred.
The fault reset function allows the drive to automatically clear a fault. The terminal set to 1E will close after the fault is
cleared and the drive has attempted to reset. If the drive cannot successfully reset within the number of attempts
permitted by L5-01, a fault will be triggered and the terminal set to 1E will open. Refer to L5: Automatic Fault Reset on
page 194 for details on automatic reset.
Setting 1F: Motor overload alarm (oL1)
The output closes when the motor overload level estimated by the oL1 fault detection exceeds 90% of the oL1 detection
level.
Setting 20: Drive overheat pre-alarm (oH)
Output closes whenever the drive heatsink temperature reaches the level specified by parameter L8-02. Refer to L8-02:
Overheat Alarm Level on page 198 for details on drive overheat detection.
Setting 2F: Maintenance period
Output closes when the cooling fan, DC bus capacitors, or DC bus pre-charge relay may require maintenance as
determined by the estimated performance life span of those components. Component performance life is displayed as a
percentage on the digital operator screen. Refer to Periodic Maintenance on page 275 for details.
Status Description
Open Elevator is being driven in up direction or stopped.
Closed Elevator is being driven in down direction.
Status Description
Open Baseblock is being executed.
Closed Drive is not in a baseblock state.
Status Description
Open Motor 1 is selected.
Closed Motor 2 is selected.
Output Speed
time
Up command
Down command
During Down Direction
OFF
ON