High Performance Vector Control/Torque Control Inverter User Manual
112
Chapter 6 Parameter Description
When the inverter operates, the function can response the setting of reference channel for other
frequencies after using the pre-set frequency as the setting frequency and keeping the time as pre-set
frequency operating time Pb.18.
Fig. 6-37 Upper and lower limit of zero frequency operation
This function supports sleep function and energy saving operation. After running, the inverter will start
when the setting frequency≥Pb.19. During operation, the inverter operates at zero frequency when the
setting frequency≤Pb.20. Proper setting of limit value of zero operation can avoid the inverter starting
and stopping frequently. If the inverter is often used for work situations such as air condition and fan,
change the analog signal of temperature sensor to setting frequency to control automatic starting or
stopping of inverter. See Fig. 6-37.
Parameters copy function can be realized through operation panel.
0: No operation. When upload or download completed, the parameter restores automatically to 0.
1: Upload parameters. Press PRG button to upload parameters to the operation panel after setting, and
will display percentage of copy process when indicating “LoAd”.
Output frequency
Temperature sensor or
anlog
signal
10V or 20mA
Operation e
tempe
rature
Temperature sensor or anlog signal
10V or 20mA
Sleep
period
Operation
temperature
T
emperature
Setting frequency
Pb.19 Upper limit of zero frequency operation
0.00~300.00 Hz(0.00Hz)
Pb.20 Lower limit of zero frequency operation 0.00~300.00 Hz(0.00Hz)
Pb.23
Parameters copy
0~5(0)
Pb.21
Reserved
0
1
0~1(0)
Pb.22
Reserved
0.0
3
8
0.0
0.0~380.0(380.0)
Output frequency