Yaskawa CIMR-UU2A0081A [488/644] H2 multi function digital outputs

Yaskawa CIMR-UU2A0042A [488/644] H2 multi function digital outputs
H1 Multi-Function Digital Input Selections
H1-oo
Setting
Function LCD Display Description Page
78
External torque
reference polarity
inversion
Tref Sign Change
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLV
Open: Forward torque reference.
Closed: Reverse polarity.
256
7E
Forward/reverse
detection
(V/f Control with
Simple
PG feedback)
PG Rotate Rev
V/f
OLV/PM
V/f w PG
AOLV/PM
OLV
CLV/PM
CLVV/f w PG
Direction of rotation detection (for V/f with Simple PG Feedback)
256
7F
PID Bi-Directional
Enable
PID BiDir Enable
All Modes
Reserved.
90 to 97
DriveWorksEZ
digital inputs 1 to 8
All Modes
Reserved for DWEZ input functions
256
9F DriveWorksEZ disabled DWEZ Disable
All Modes
Open: DWEZ enabled
Closed: DWEZ disabled
256
u
H2: Multi-Function Digital Outputs
No.
(Addr.
Hex)
Name LCD Display Description Values Page
H2-01
(040B)
Terminal M1-M2
function selection
(relay)
M1-M2 Func Sel
All Modes
Refer to H2 Multi-Function Digital Output Settings on pages
489 to 491 for descriptions of setting values.
Default: 0
Range: 0 to 192
256
H2-02
(040C)
Terminal M3-M4
function selection
(relay)
P1/PC Func Sel
Default: 1
Range: 0 to 192
256
H2-03
(040D)
Terminal M5-M6
function selection
(relay)
P2/PC Func Sel
Default: 2
Range: 0 to 192
256
H2-06
(0437)
Power Consumption
Output Unit Selection
Pwr Mon Unit Sel
All Modes
Sets the units for the output signal when Power Consumption
Pulse Output is selected as the digital output (H2-01, H2-02, or
H2-03 = 39).
0: 0.01 kWh units
<1>
1: 1 kWh units
2: 10 kWh units
3: 100 kWh units
4: 1000 kWh units
Default: 1
Range: 0 to 4
266
H2-07
(0B3A)
MEMOBUS Register 1
Address Select
MFDO Regs1 Addr
All Modes
Sets the addresses of the MEMOBUS/Modbus registers from
which data will be sent to contact outputs 62 and 162.
Default: 1
Range: 1 to
1FFFH
267
H2-08
(0B3B)
MEMOBUS Register 1
Bit Select
MFDO Regs1 Bit
All Modes
Sets the bits for the MEMOBUS/Modbus registers from which
data will be sent to contact outputs 62 and 162.
Default: 0
Range: 0 to
FFFFH
267
H2-09
(0B3C)
MEMOBUS Register 2
Address Select
MFDO Regs2 Addr
All Modes
Sets the addresses of the MEMOBUS/Modbus registers from
which data will be sent to contact outputs 63 and 163.
Default: 1
Range: 1 to
1FFFH
267
H2-10
(0B3D)
MEMOBUS Register 2
Bit Select
MFDO Regs2 Bit
All Modes
Sets the bits for the MEMOBUS/Modbus registers from which
data will be sent to contact outputs 63 and 163.
Default: 0
Range: 0 to
FFFFH
267
<1> Available in drive software versions PRG: 1015 and later.
B.9 H Parameters: Multi-Function Terminals
488
YASKAWA ELECTRIC SIEP C710636 04C U1000 Industrial MATRIX Drive Technical Manual