Yaskawa CIMR-UU2A0130A [524/644] B 5 u monitors

Yaskawa CIMR-UU4A0021A [524/644] B 5 u monitors
No.
(Addr.
Hex)
Name LCD Display Description
Analog
Output Level
Unit
U4-03
(0067)
<2>
Cooling Fan Operation
Time
Fan Elapsed TIme
All Modes
Displays the cumulative operation time of the cooling fan. The
default value for the fan operation time is reset in parameter
o4-03. This value will reset to 0 and start counting again after
reaching 99999.
No signal output
available
1 h
U4-04
(007E)
Cooling Fan
Maintenance
Fan Life Mon
All Modes
Displays main cooling fan usage time as a percentage of its
expected performance life. Parameter o4-03 can be used to reset
this monitor.
Replace the fan when this monitor reaches 90%.
No signal output
available
1%
U4-05
(007C)
Capacitor Maintenance Cap Life Mon
All Modes
Displays control circuit capacitor usage time as a percentage of
their expected performance life. Parameter o4-05 can be used to
reset this monitor.
Replace the capacitor when this monitor reaches 90%.
No signal output
available
1%
U4-06
(07D6)
Soft Charge Bypass
Relay Maintenance
ChgCirc Life Mon
All Modes
Displays the soft charge bypass relay maintenance time as a
percentage of its estimated performance life. Parameter o4-07
can be used to reset this monitor.
Replace the soft charge bypass relay when this monitor reaches
90%.
No signal output
available
1%
U4-08
(0068)
Heatsink Temperature Heatsink Temp
All Modes
Displays the heatsink temperature.
10 V: 100 °C 1 °C
U4-09
(005E)
LED Check LED Oper Check
All Modes
Lights all segments of the LED to verify that the display is
working properly.
No signal output
available
U4-13
(07CF)
Peak Hold Current Current PeakHold
All Modes
Displays the highest current value that occurred during run.
No signal output
available
0.01 A
<3> <4>
<5>
U4-14
(07D0)
Peak Hold Output
Frequency
Freq@ I PeakHold
All Modes
Displays the output frequency when the current value shown in
U4-13 occurred.
No signal output
available
0.01 Hz
U4-16
(07D8)
Motor Overload
Estimate (oL1)
Motor OL1 Level
All Modes
Shows the value of the motor overload detection accumulator.
100% is equal to the oL1 detection level.
10 V: 100% 0.1%
U4-18
(07DA)
Frequency Reference
Source Selection
Reference Source
All Modes
Displays the source for the frequency reference as XY-nn.
X: indicates which reference is used:
1 = Reference 1 (b1-01)
2 = Reference 2 (b1-15)
Y-nn: indicates the reference source
0-01 = Digital operator
1-00 = Analog
1-01 = Analog (terminal A1)
1-02 = Analog (terminal A2)
1-03 = Analog (terminal A3)
2-02 to 17 = Multi-step speed (d1-02 to 17)
3-01 = MEMOBUS/Modbus communications
4-01 = Communication option card
5-01 = Pulse input
7-01 = DWEZ
9-01 = Up/Down Command
No signal output
available
U4-19
(07DB)
Frequency Reference
from MEMOBUS/
Modbus Comm.
MEMOBUS Freq Ref
All Modes
Displays the frequency reference provided by MEMOBUS/
Modbus (decimal).
No signal output
available
0.01%
U4-20
(07DC)
Option Frequency
Reference
Option Freq Ref
All Modes
Displays the frequency reference input by an option card
(decimal).
No signal output
available
B.15 U: Monitors
524
YASKAWA ELECTRIC SIEP C710636 04C U1000 Industrial MATRIX Drive Technical Manual