Technical Data
Installation MaintenanceWiring
and replace
with
DSM
210-xxDC
Green LED ON = OK
Green LED OFF = Defect
X
Installation
+
PE
F2
DS210-xxDC Series
DS210-12DC
DS210-24DC
DS210-48DC
DS210-75DC
DS210-95DC
DS210-110DC
DS210-130DC
DS210-48DC/SCL
DS210-75DC/SCL
Un (Vdc)
12 24 48 75 48 7595 110 130
2 6
6500 ft max.
2000 m ma
x.
-40/+185°F max.
-40/+85°C max.
IP20
indoor use only
P/N
F1
F2
F1
SPD
Standard wiring
F1
SPD
V-diagram wiring
INSTALLATION INSTRUCTIONS -
NOTICE D'INSTALLATION
NOTICIA DE INSTALACIÓN - INSTALLATIONSHINWEISE
ISTRUZIONI PER L'INSTALLAZIONE
INSTRUCOES DE INSTALACAO - MONTÁŽNÍ NÁVOD
РУКОВОДСТВО ПО МОНТАЖУ - 安装指导书
DC surge protector -
Parafoudre DC
Überspannungsschutz für DC - DC contra sobretensiones
Protezione DC - Proteção DC - Svodiče přepěti pro DC
Устройство защиты от импульсных
перенапряжений для сетей DC - 直流浪涌保护器
protected
equipment
DC power
source
Imax (kA)
< 0.1IPE (mA)
F2
F1
SPD
∑ a+b+c
≤ 50 cm
a
b
c
F1
SPD
≤ 50 cm
1.5 - 16 mm
2
15 - 5 AWG
1.5
- 10 mm
2
15 - 7 AWG
min-max
5
1.2 - 1.5 Nm
10.6 - 13.3 Lb-In
4
16 mm
0.63 in
13 mm
0.5 in
2.5 - 35 mm
2
13 - 2 AWG
2.5
- 25 mm
2
13 - 4 AWG
min-max
1
Clip on
symmetrical
DIN rail
3
2 - 2.5 Nm
18 - 22 Lb-In
2
N150403
DC Network
Characteristics
DS210-xxDC version DS210-xxDC/SCL version
X
Note:
No maintenance.
These devices are designed for a end of life by internal
short-circuit that will be activated only in
exceptional conditions (example : several secondes
without eect on the fuses or circuit breakers
to installation).
In this case :
- The SPD will go in short-circuit to the network.
- The upstream in-line protection (fuse or breaker)
will open.
Then the plugabble module DSM210-xxDC/SCL
must be replaced by an Electrically operator.
F1 10 A F1 20 A
F1 > 10 A
F2
No F2
=
10 A
F1 > 20 A
F2
=
20 A
1 2
F2 F1
* *
No F2
1 2
F2 F1
* *
* depending on national rules : Solution or
1 2
DS210-xxDC DS210-xxDC/SCL
Internal
Short-circuit