2. Installation
2.5 Connections with a FlexPDU (Power Distribution Unit) module (optional)
2.6 Connections with a HotSwap MBP module (optional)
The HotSwap MBP module makes it possible to service or even replace the UPS without affecting the connected
loads (HotSwap function).
1 - Connect the UPS socket (10) to the AC-
power source using the cable (31)
supplied.
2 - Connect the input socket on the
FlexPDU module (48) to the UPS outlet (7)
using the cable (41) supplied. The cable
and the connectors are marked in red.
3 - Connect the equipment to the outlets
(45), (46) and (47) on the FlexPDU module.
These outlets differ, depending on the
version of the FlexPDU module.
4 - Fit the connection securing system that
prevents the plugs from being pulled out
accidentally.
1 - Connect the input socket (56) on the
HotSwap MBP module to the AC-power
source using the cable (31) supplied.
2 - Connect the UPS input socket (10) to
the "UPS Input" (55) on the HotSwap MBP
module, using the cable (44) supplied.
These cables and the connectors are
marked blue.
3 - Connect the UPS outlet (7) to the "UPS
Output" (54) on the HotSwap MBP
module, using the cable (44) supplied.
These cables and the connectors are
marked red.
4 - Connect the equipment to the outlets
(49) and (50) on the HotSwap MBP
module. These outlets differ, depending
on the version of the HotSwap MBP
module.
Caution. Do not use UPS outlets (8) and
(9) to supply equipment because use of
switch (53) on the HotSwap MBP module
would cut supply to the equipment. It is
advised not to remove the protective film
from outlets (8) and (9).
7
8
9 10
48474645
FlexPDU
41
31
7
8
9 10
By-pass
Normal
UPS ON -
OK to switch
BY PASS SWITCH
56
5549
HotSwap MBP
50
545351 52
44
31