Wiring Layout ESIE 05-07
1–164 Part 1 – System Outline
Power supply RS485 connection Analogue input
Analogue output
(Converted to digital outputs = DO)
Digital input Digital output
J1-G: 24Vac
J1-G0: Reference (GND)
J11-TX-
J11-TX+
J11-GND
J2 (B1-VDC): High pressure C1
J2 (B2-VDC): Low pressure C1
J2 (B3-GND): Changeable AI1
J3 (B4-BC4): Evap Inlet water sensor
J3 (B5-BC5): Evap mixed outlet water C1
J6 (B6-GND): Ambient sensor
J6 (B7-VDC): Capacity feedback of C1
J4 (VG0-Y1): Ctrl motor loadup C1 J5 (ID1-IDC1): High pressure switch C1
J5 (ID2-IDC1): Reverse phase protector C1
J5 (ID3-IDC1): Overcurrent relay C1
J5 (ID4-IDC1): Discharge thermal prot C1
J5 (ID5-IDC1): Compr thermal prot C1
J5 (ID6-IDC1): Emergency stop
J5 (ID7-IDC1): Flowswitch C1
J5 (ID8-IDC1): Changeable DI 1
J7 (ID9-IDC9): Changeable DI 2
J7 (ID10-IDC9): Changeable DI 3
J7 (ID11-IDC9): Changeable DI 4
J12 (C1-NO1): Compr star C1
J12 (C1-NO2): Compr delta C1
J12 (C1-NO3): Compr on C1
J13 (C4-NO4): 12 C1
J13 (C4-NO5): --
J13 (C4-NO6): --
J14 (C7-NO7): Alarm
J15 (C8-NO8): Pump
J16 (C9-NO9): --
Digital output Overview of changeable digital inputs DI 1-2-3-4 Overview of changeable analog input AI 1
Overview of changeable digital outputs DO
1-2
J16 (C9-NO9): Fanstep 1 of C1
J16 (C9-NO10): Fanstep 2 of C1
J16 (C9-NO11): Fanstep 3 of C1
J17 (C12-NO12): Changeable DO1
J18 (C13-NO13): Changeable DO2
J5 (ID8-IDC1):
J7 (ID9-IDC9):
J7 (ID10-IDC9):
J7 (ID11-IDC9):
Dual setpoint / Remote On -Off / enable / disable capacity
limitation 1-2-3-4
J2 (B3-GND): Setp Signal 0-1V / 0-10V / 0-20mA /
4-20mA
(only standalone unit or Slave1)
J17 (C12-NO12):
J18 (C13-NO13): 2nd evaporator pump / Con-
denser pump / 100 capacity / reversing valve /
general operation