Functional Control for a Standalone Unit ESIE05-07
2–52 Part 2 – Functional Description
3
1
2
4
5
2.15 Changeable Digital Inputs
Introduction 4 changeable digital inputs are available and can be assigned to 10 different functions in the service
menu.
Range of
application
Functions overview
Remark: the selected function will only be accepted if it hasn't already been assigned to another digital
input.
(*): DI1 is default programed as “heat recovery”.
Input Parameter
on
controller
Air-cooled Evaporator
-less
Water-
cooled
Condenser
-less
EWAP/
EWAD
EWTP ERAP EWWD EWLD
CO HR CA HP RC
DI8 DI1 O O O O O
DI9 DI2 O O O O O
DI10 DI3 O O O O O
DI11 DI4 O O -- O O
Possible functions
Air-cooled Evaporator-
less
Water-
cooled
Condenser-
less
EWAP/
EWAD
EWTP ERAP EWWD EWLD
CO HR CA HP RC
0. None O O O O O
1. Status O O O O O
2. Dual setpoint O O -- O O
3. Remote On -Off O O O O O
4. Remote Cooling /
Heating
-- -- -- O --
5/6/7/8. Capacity limi-
tation 1-2-3-4
OO O O O
9. Fan Low noise O O O -- O
10. Heat Recovery -- O -- -- --
ESIE05-07.book Page 52 Wednesday, October 11, 2006 10:42 AM