EWAP400~540MBYNN
Packaged air-cooled water chillers
4PW22679-1B
Operation manual
10
Safeties menu
The "safeties" menu provides useful information for trouble shooting
purposes. The following screens contain basic information.
Along with the basic information, more detailed information screens
can be consulted while the safety menu is active. Press the q key.
Screens similar to the following will appear.
History menu
The "history" menu contains all the information concerning the latest
shutdowns. The structure of those menus is identical to the structure
of the safeties menu. Whenever a failure is solved and the operator
performs a reset, the concerning data from the safeties menu is
copied into the history menu.
Additionally the number of safeties that already occured, can be
consulted on the first line of the history screens.
Info menu
Input/output menu
The "input/output" menu gives the status of all the digital inputs and
the relay outputs of the unit.
To check the actual value of the
compressor startup timers and the stop
timers.
To consult information about the unit
safety which caused the shutdown.
To consult information about the
circuit 1 safety which caused the
shutdown.
To consult information about the
circuit 2 safety which caused the
shutdown.
To consult information about the
network safety which caused the
shutdown.
To consult information about the dual
pump which caused the shutdown.
To check the time and control mode
at the moment of the unit shutdown.
To check which were the evaporator
and condenser inlet water
temperature and the evaporator
outlet water temperature.
To check which was the evaporator
outlet water temperature of the circuit
and the thermostat step at the
moment of shutdown.
To check which was the status of the
compressors at the moment of
shutdown.
To check which were the pressures of
circuit 1 at the moment of shutdown.
To check which were the pressures of
circuit 2 at the moment of shutdown.
To check which were the total amount of
running hours of the compressors and
the ambient temperature at the moment
of shutdown.
'0
%%%4 %%4
%%%4 %%4
'(
%
'(
'(
'(
%# &
'(
%
'( %%
%
%%2%% %%%
'( %%
%
&&%
&%!&%
'( %%
%
&%!&%
&%!&%
'( %%
%
'( %%
%
+&%, - .%&/
#&#, - .&
'( %%
%
+&%, - .%&/
#&#, - .&
'( %%
%
%%%%%2 &
%%%%%2 %&%
To consult time and date information.
To consult additional information about
the unit such as the unit type and the
refrigerant used.
To consult information about the
controller's software version.
To consult information about the
PCB.
To check whether or not the emergency
stop device is active and if there's any
water flow to the evaporator.
To check the status of the high pressure
switch, the reverse phase protector and
overcurrent relay for circuit 1.
To check whether or not the discharge
thermal protector or the compressor
thermal protector are activated for
circuit 1.
To check the status of the high pressure
switch, the reverse phase protector and
the overcurrent relay for circuit 2.
To check whether or not the discharge
thermal protector or the compressor
thermal protector are activated for
circuit 2.
To check the status of the changeable
digital inputs.
Note that for a unit in a DICN system,
the inputs apply to this unit.
It will be the remote input on the master
unit however, that will be determining
for the operation of the unit.
To check the status of the power relays
of circuit 1.
To check the status of the power relays
of circuit 2.
To check the capacity mode and
feedback of circuit 1.
To check the capacity mode and
feedback of circuit 2.
To check the status of the fanspeed
relays of circuit 1.
'(
%%2%%
%%%
')
#%%
"
#%!
')
#&%$ %%/%.
'0
"&%.%#%
"&$%.%#
6 %
'(
&
&
')
&&
&&&
')
&&&
&&&
')
&&
&&&
')
&&&
&&&
')& &
"
')
')
')
*
%"%&%7
')
*
%"%&%7
')
"
Содержание
- Operation manual 1
- Packaged air cooled water chillers 1
- Electrical specifications 2
- Important information regarding the refrigerant used 2
- Introduction 2
- Operation manual 2
- Technical specifications 2
- Description 3
- Escription 3
- Function of the main components 4
- Safety devices 4
- Internal wiring parts table 5
- Before operation 6
- Checks before initial start up 6
- General recommendations 6
- Operation 6
- Power supply connection and crankcase heating 6
- Water supply 6
- Digital controller 7
- Operation 7
- Peration 7
- Working with the unit 7
- Consulting actual operational information 8
- Switching the unit off 8
- Switching the unit on 8
- Switching units on off in a dicn system 8
- Adjusting the temperature setpoint 9
- Resetting the unit 9
- Advanced features of the digital controller 10
- All menus are directly accessible using the corresponding key on the digital controller the down arrow x on the display indicates that you can go to the next screen of the current menu using the h key the up arrow w on the display indicates that you can go to the previous screen of the current menu using the g key if c is displayed this indicates that you can either return to the previous screen or can go to the next screen 10
- Depending upon the settings in the user settings menu the 10
- Menu can either be entered directly or by means of the user password 10
- Menu protected by the user password allows a full customization of the units 10
- Readout menu 10
- Setpoint 10
- Setpoints menu 10
- This chapter gives an overview and a brief functional description of the screens provided by the different menus in the following chapter you will find how you can set up and configure the unit using the various menu functions 10
- Timers menu 10
- User setting 10
- User settings menu 10
- Additionally the number of safeties that already occured can be consulted on the first line of the history screens 11
- Along with the basic information more detailed information screens can be consulted while the safety menu is active press the q key screens similar to the following will appear 11
- Histor 11
- History menu 11
- Info menu 11
- Input outpu 11
- Input output menu 11
- Menu contains all the information concerning the latest shutdowns the structure of those menus is identical to the structure of the safeties menu whenever a failure is solved and the operator performs a reset the concerning data from the safeties menu is copied into the history menu 11
- Menu gives the status of all the digital inputs and the relay outputs of the unit 11
- Menu provides useful information for trouble shooting purposes the following screens contain basic information 11
- Safetie 11
- Safeties menu 11
- To check the actual value of the compressor startup timers and the stop timers 11
- To check the capacity mode and feedback of circuit 1 11
- To check the capacity mode and feedback of circuit 2 11
- To check the status of the changeable digital inputs note that for a unit in a dicn system the inputs apply to this unit it will be the remote input on the master unit however that will be determining for the operation of the unit 11
- To check the status of the fanspeed relays of circuit 1 11
- To check the status of the high pressure switch the reverse phase protector and overcurrent relay for circuit 1 11
- To check the status of the high pressure switch the reverse phase protector and the overcurrent relay for circuit 2 11
- To check the status of the power relays of circuit 1 11
- To check the status of the power relays of circuit 2 11
- To check the time and control mode at the moment of the unit shutdown 11
- To check whether or not the discharge thermal protector or the compressor thermal protector are activated for circuit 1 11
- To check whether or not the discharge thermal protector or the compressor thermal protector are activated for circuit 2 11
- To check whether or not the emergency stop device is active and if there s any water flow to the evaporator 11
- To check which was the evaporator outlet water temperature of the circuit and the thermostat step at the moment of shutdown 11
- To check which was the status of the compressors at the moment of shutdown 11
- To check which were the evaporator and condenser inlet water temperature and the evaporator outlet water temperature 11
- To check which were the pressures of circuit 1 at the moment of shutdown 11
- To check which were the pressures of circuit 2 at the moment of shutdown 11
- To check which were the total amount of running hours of the compressors and the ambient temperature at the moment of shutdown 11
- To consult additional information about the unit such as the unit type and the refrigerant used 11
- To consult information about the circuit 1 safety which caused the shutdown 11
- To consult information about the circuit 2 safety which caused the shutdown 11
- To consult information about the controller s software version 11
- To consult information about the dual pump which caused the shutdown 11
- To consult information about the network safety which caused the shutdown 11
- To consult information about the pcb 11
- To consult information about the unit safety which caused the shutdown 11
- To consult time and date information 11
- Defining and activating the control mode 12
- Defining the lead lag mode 12
- Defining the thermostat settings 12
- Entering the user settings menu 12
- Network menu 12
- User password menu 12
- Defining dual evaporator pump control 13
- Defining free cooling 13
- Defining the capacity limitation settings 13
- Defining the display settings 13
- Defining the pump control settings 13
- Defining the schedule timer 13
- Defining the floating setpoint settings 13
- Activating or deactivating the setpoints password 14
- Checking the actual value of the software timers 14
- Defining bms control 14
- Defining the network settings 14
- Checking the safety info and the unit status after a reset 15
- Checking the status of the inputs and outputs 15
- Consulting additional unit information 15
- Listing activated safeties and checking the unit status 15
- Changing the user password 16
- Roubleshooting 16
- Troubleshooting 16
- Aintenance 18
- Disposal requirements 18
- Maintenance 18
- Maintenance activities 18
- Inlet water temperature control outlet water temperature control 19
- Schedule timer example 19
- Thermostat parameters 19
- Floating setpoint working 20
- Free cooling on ambient temperature 20
- Free cooling on difference between inlet water evaporator temperature and ambient temperature 20
- Free cooling working 20
- Oftware structure 21
- Q q q q 21
- Pw22679 1b 22
Похожие устройства
- Daikin EWAP540MBYN Инструкция по монтажу
- Daikin EWAP540MBYN Технические данные
- Daikin EWAP540MBYN Сервис мануал
- Daikin EWWD340CJYNN Инструкция оператора
- Daikin EWWD340CJYNN Инструкция по монтажу
- Daikin EWWD340CJYNN Технические данные
- Daikin EWWD340CJYNN Сервис мануал
- Daikin EWWD400CJYNN Инструкция оператора
- Daikin EWWD400CJYNN Инструкция по монтажу
- Daikin EWWD400CJYNN Технические данные
- Daikin EWWD400CJYNN Сервис мануал
- Daikin EWWD480CJYNN Инструкция оператора
- Daikin EWWD480CJYNN Инструкция по монтажу
- Daikin EWWD480CJYNN Технические данные
- Daikin EWWD480CJYNN Сервис мануал
- Daikin EWWD550CJYNN Инструкция оператора
- Daikin EWWD550CJYNN Инструкция по монтажу
- Daikin EWWD550CJYNN Технические данные
- Daikin EWWD550CJYNN Сервис мануал
- Daikin EWWD700CJYNN Инструкция оператора