Daikin EWAP540MBYN [12/22] Defining and activating the control mode

Daikin EWAP460MBYN [12/22] Defining and activating the control mode
Operation manual
11
EWAP400~540MBYNN
Packaged air-cooled water chillers
4PW22679-1B
User password menu
Network menu
The "network" menu provides useful information regarding the
network.
Tasks of the user settings menu
Entering the user settings menu
The user settings menu is protected by the user password, a 4-digit
number between
%%%%
and
++++
.
1 Enter the
 &
(Refer to the chapter "How to
enter a menu" on page 6).
The controller will request the password.
2 Enter the correct password using the g and h keys.
3 Press q to confirm the password and to enter the user settings
menu.
The controller automatically enters the first screen of the user
settings menu.
To define settings of a certain function:
1 Go to the appropriate screen of the usersettings menu using the
g and h keys.
2 Position the cursor behind the parameter to be modified using
the q key.
3 Select the appropriate setting using the g and h keys.
4 Press q to confirm the selection.
When the selection has been confirmed, the cursor switches to
the next parameter which can now be modified.
5 Repeat from instruction 2 onwards to modify the other
parameters.
Defining and activating the control mode
The unit is equipped with a thermostat which controls the cooling
capacity of the unit. Three different control modes exist:
manual control mode: the operator controls the capacity
himself -
 
- by setting:
3
,
3
(airflow of circuit 1, 2 in manual mode): off, low, medium
or high.

,

(capacitystep of circuit 1, 2 in manual mode: 0%,
30%~100%.
inlet control mode: uses the evaporator entering water
temperature to control the capacity of the unit -
 
outlet control mode: uses the evaporator leaving water
temperature to control the capacity of the unit -
 
Defining the thermostat settings
When automatic control mode is selected, the unit uses a thermostat
function to control the cooling capacity. However, the thermostat
parameters are not fixed and can be modified via the
&

screen of the user settings menu.
The default, limit and step values for the thermostat parameters are
shown in "Annex I" on page 18.
Defining the lead-lag mode
The lead/lag mode determines which of both circuits starts up first in
case of a capacity demand.
The lead-lag parameters are :
 
Automatic: the controller decides whether circuit 1 or circuit 2
starts up first.
Manual C1>C2: circuit 1 starts up before circuit 2. If circuit 1 is
de-activated due to a failure, circuit 2 will start up instead.
Manual C2>C1: circuit 2 starts up before circuit 1. If circuit 2 is
de-activated due to a failure, circuit 1 will start up instead.
 
In the automatic mode, the number of hours indicated on the
display is the maximum difference between the running hours of
both circuits. This value is important for maintenance purposes.
It should be set high enough so that both circuits do not require
maintenance at the same time and that at least one circuit can
remain constantly active.
The lower and upper limits are 100 and 1000 hours respectively.
The default value is 1000 hours.
5 
If this parameter is set on
(Yes), both circuits will try to go up in
capacity alternatingly.
If this parameter is set on
(No), the leading circuit will try to go
to full capacity before the lagging circuit can startup.
To check the status of the fanspeed
relays of circuit 2.
To check the status of the pump, the
alarm and the evaporator heater voltage
free contacts.
To check the status of the changeable
relay output.
To change the user password.
To consult the temperature setpoint, the
common entering water temperature
(entering water temperature of the
master unit) and the common leaving
water temperature (only displayed when
 
mode is set and the
optional common leaving water sensor
(R8T) is installed). Refer to "Defining
and activating the control mode" on
page 11.
The status screen of the network menu
shows the condition of the master unit
(
) and slave units (

...
"
).
')  
  
  
  "
')  
& 
 

'0& 
# 
 && 
    
'  
 %%%%
%%%%
'( 
  &%
   &%
'0  %%*
 %%*
&%%*
" %%*
NOTE
To activate manual control mode, select

as
present mode. To de-activate the manual control
mode, select
 
or
 
as
present mode.
For units in a DICN configuration:
When changing the control mode on one of the
units, it is automatically transferred to all other
units.
Manual control mode however can only be
selected on units with status
 

.
NOTE
If changed on one of the units in a DICN
configuration, this setting is transferred to all other
units in the network.
A functional diagram showing the thermostat
parameters can be found in "Annex I" on page 18.

Содержание

Скачать