Daikin EWWD400CJYNN [15/28] Main menu

Daikin EWWD480CJYNN [15/28] Main menu
15
(=maint): by entering a password, it is possible to access the maintenance functions
menu: it allows to view the main menu
info: it allows to go from one board to another (showing the parameters of the corresponding compressor)
It allows to change over from chiller to heat pump (only if enabled)
It allows to change over from heat pump to chiller (only if enabled)
on/off: unit On/Off key.
alarm: It indicates the presence of possible malfunctions and their causes
(=up): It is used to return to previous screen
(=down) : It is used to shift to next screen
enter: It confirms the set values
It is possible to access the different sections of program through the keypad. There are actually 9 screen categories as
summarized in the table below, which includes the access keys for each screen along with a description of the category.
CATEGORY DESCRIPTION KEYS PASSWORD
Main Unit operational parameters (view only)
menu
NO
User User parameters setting
prog
YES
Setting Setpoint setting
set
NO
Input/Output Compressors operational parameters (view only)
I/O
NO
Manufacturer Manufacturer parameters setup
Menu+prog
YES
Maintenance Access to maintenance parameters
maint
NO/YES
Maint auxiliary Setting of auxiliary maintenance parameters
menu+maint
YES
Alarm Alarms view
alarm
NO
Alarm buffer 10 recorded previous alarms
menu+ alarm
NO
The password remains valid for 10 minutes after last access.
5.3 Main menu
This section shows only the output parameters through subsequent screens (it is possible to shift from one screen to the
next by using the arrow key):
Current date, time and weekday, setpoint origin and unit load percentage, including the following information:
- Off Alarm: unit shut down due to alarm condition
- Off Rem Comm: unit switched off remotely (supervisor or BMS)
- Off Time Schedule : unit off as per current time schedule
- Off Loc/Remote Sw: unit off through switch
- Off Keypad: unit switched off through the keypad on/off key
- Off Amb. LockOut: unit Off on low ambient temperature (or tower return temperature)
- Waiting flow: unit On waiting for evaporator water flow
- Waiting load: unit On, but compressors not running because of low load requirements.
- No comps available: unit On with no compressors available for automatic management (compressors switched
OFF or in alarm condition or in manual mode)
Unit limiting status (if enabled)