5.9 Service Menu
Service parameters can be defined in this section by entering a password and accessing the followings forms:
• Compressor control (OFF/AUTO/MANUAL) and compressor load in manual mode
• Alarms reset
• SoftLoad reset
• Oil heating reset
5.10 Alarms Menu
When an alarm condition occurs, the display BUZZER sounds. By pressing the alarm key, the current fault is displayed.
By pressing the alarm key twice, the buzzer is stopped, and by pressing it three times the alarm is cleared.
REMARK: Sometimes, after an alarm has occurred, it is possible that also a spurious alarm of star/delta transition failed
occurs; in this case fix the earlier alarm first and, only if the spurious one occurs again, check the electrical connections.
If the alarm is not cleared after pressing again the alarm key, it means that the fault conditions persists.
5.11 Buffer Alarm Menu
The last ten alarms of every chiller circuit are stored in this section.
Each form displays the date, the time and the description of the alarm. By pressing the enter key when an alarm
description is displayed, the operating conditions at the time the alarm occurred (temperatures, pressures, expansion
valve status and compressor load) are shown.
5.12 Alarm List
In the following table, the list of the possible alarms with the identifier number, the cause and the reset type (A = auto,
M = manual) is shown
Alarm Alarm cause Reset
001 Phase monitor Activation of the phase control device. M
002 Freeze alarm Antifreeze protection. The outlet water temperature is equal to
the antifreeze value.
M
005 Evaporator Flow alarm Action by evaporator flow switch in a low flow condition. The
water pump might be off
M
006 Low pressure alarm Low oil pressure. M
007 High discharge temperature switch Action by discharge temperature switch M
008 Fault transition Starting procedure is not complete. Verify correct sequence M
009 Low oil pressure The oil pressure is not enough for the correct lubrication of the
compressor. Verify that the condensation pressure is sufficient.
M
010 Low pressure switch
011 High oil pressure difference High oil differential pressure. The oil filter might be dirty. M
012 High pressure switch Action by high pressure mechanical switch M
016 Compressor overload Action by thermal protection of compressor motor or by high
temperature switch
M
023 High pressure alarm Action by microchip on high pressure M
030 B1 sensor /input faulty or not
connected
M
031 B2 sensor /input faulty or not
connected
M
032 B3 sensor /input faulty or not
connected
M
033 B4 sensor /input faulty or not
connected
M
034 B5 sensor /input faulty or not
connected
M
035 B6 sensor /input faulty or not
connected
M
036 B7 sensor /input faulty or not
connected
M
037 B8 sensor /input faulty or not
connected
M
039 Evaporator pump maintenance Request for evaporator pump maintenance M
Содержание
- Contents 2
- General description 2
- Main features of control software 4
- Components description 5
- Main board 6
- Eexv valve driver 7
- Addressing of plan 8
- Alarms that will shutdown the system 8
- Meaning of the eexv driver status leds 8
- Other alarms 8
- Air cooled chillers unit config 00 9
- Analogue inputs analogue inputs n compressor 1 compressor 2 compressor 3 compressor 4 9
- Controller input output 9
- Digital inputs 9
- N compressor 1 compressor 2 compressor 3 compressor 4 9
- Analogue inputs n compressor 1 compressor 2 compressor 3 compressor 4 10
- Analogue outputs n compressor 1 compressor 2 compressor 3 compressor 4 10
- Digital inputs n compressor 1 compressor 2 compressor 3 compressor 4 10
- Digital outputs n compressor 1 compressor 2 compressor 3 compressor 4 10
- Water cooled heat pump or pursuit unit config 01 or 02 10
- Analogue outputs n compressor 1 compressor 2 compressor 3 compressor 4 11
- Digital inputs 11
- Digital outputs n compressor 1 compressor 2 compressor 3 compressor 4 11
- N compressor 1 compressor 2 compressor 3 compressor 4 11
- Water cooled chillers unit config 03 11
- Analogue inputs n compressor 1 compressor 2 compressor 3 compressor 4 12
- Analogue outputs n compressor 1 compressor 2 compressor 3 compressor 4 12
- Digital analogue outputs n compressor 1 compressor 2 compressor 3 compressor 4 12
- Display and keypad 13
- General description 13
- Gg mm aa sat hh mm 13
- Unit status cooling staging xxx stp source local 13
- Keypad keys and their functions 14
- Category description keys password 15
- Main menu 15
- User menu 16
- Input output menu i o menu 17
- Manufacturer menu 17
- Setting menu 17
- Warning 17
- Maintenance menu 18
- Alarm list 19
- Alarms menu 19
- Buffer alarm menu 19
- Service menu 19
- Description of the compressor capacity control 20
- Setting of the capacity transducer 20
- Water temperature setpoint reset 20
- Soft load 21
- Start up inhibition 21
- Start up with high evaporator water temperature 21
- Unit limitation 21
- Appendix 1 software upload to the controller 22
- Dire c t upload from a pc 22
- Upload from programming key 23
- Appendix 2 unit start up sequence 24
- In the following paragraphs the unit start up management and shutdown procedures are shown in addition to this the compressors loading and unloading strategy is shown 24
- Unit startup and compressors management 24
- Appendix 3 plan settings 27
Похожие устройства
- Daikin EWWD700CJYNN Инструкция по монтажу
- Daikin EWWD700CJYNN Технические данные
- Daikin EWWD700CJYNN Сервис мануал
- Daikin EWWD750CJYNN Инструкция оператора
- Daikin EWWD750CJYNN Инструкция по монтажу
- Daikin EWWD750CJYNN Технические данные
- Daikin EWWD750CJYNN Сервис мануал
- Daikin EWWD800CJYNN Инструкция оператора
- Daikin EWWD800CJYNN Инструкция по монтажу
- Daikin EWWD800CJYNN Технические данные
- Daikin EWWD800CJYNN Сервис мануал
- Daikin EWWD900CJYNN Инструкция оператора
- Daikin EWWD900CJYNN Инструкция по монтажу
- Daikin EWWD900CJYNN Технические данные
- Daikin EWWD900CJYNN Сервис мануал
- Daikin EWWD950CJYNN Инструкция оператора
- Daikin EWWD950CJYNN Инструкция по монтажу
- Daikin EWWD950CJYNN Технические данные
- Daikin EWWD950CJYNN Сервис мануал
- Daikin EWWDC10CJYNN Инструкция оператора