Daikin EWWD700CJYNN [21/28] Start up with high evaporator water temperature
21
4. From evaporator water Delta T: A reduction in the evaporator water Delta T -adjustable under "User" password-
corresponds to an increase in the setpoint for refrigerated water temperature control. Such control logic allows
electric energy savings when the unit works at partial load.
8. Unit Limitation
This function is useful in all those situations where a reduction in the electric consumption of the unit is necessary
during certain hours of the day.
It is possible to limit the power consumption of the unit by using any of the two options available under “User”
password.
The first way, called “Demand limit” requires a 4-20mA external signal; the unit max load decreases from 100% to 0%
as the input increase from 4mA to 20mA. Inputs lower than 4mA have no effect on the unit.
The second way, called “Current limit” requires a direct measurement of the current absorbed by the unit and the setting
of the maximum current to be absorbed (optional).
9. Soft load
This function, which can be accessed through the keypad under “User” password, limits unit load to a preset value for a
pre-determined period of time after unit start-up. This function is applicable in situations where the water temperature is
high at the start-up but thermal load is not consistently high. This logic allows to save energy during the load reduction
period by preventing the compressors from unnecessarily increasing and then decreasing their capacity.
10. Start-up with high evaporator water temperature
This function limits the load of each compressor to a set value (default 70%), until the water outlet temperature is over
the set value (default 25°C). Such logic helps start the group of chillers when the water temperature is initially very high
(35-40°C).
This feature prevents from dangerous superheating of the motor and undesirable triggering of the high pressure
protection. The values of maximum compressor load and water temperature limit are modifiable under "User" password.
11. Start-up inhibition
The controller can manage the start-up and the shut down of the unit in accordance with manifold logics in function of
the requested application.
Local On/Off: unit shutdown through controller (On/Off key). If the switch is enabled, "Off Keypad" will appear on the
status display of the unit
Remote On/Off: unit shutdown through digital contact.
If the panel switch is in the “0” position the unit is off by local switch and on the display will appear “Off Loc/Rem Sw”.
If the switch is in “Loc” position the unit is on (unless other shutdown conditions prevail).
When the switch in "Rem" position, the digital contact control allows the start-up and the shutdown of the unit from a
remote location. When the unit is stopped remotely, "Off Loc/Rem Sw”" will appear on the status display of the unit
On/Off Network: this function allows the start-up and the shutdown of the unit through a supervisory system. If the
function is enabled, "Off Rem" will appear on the status display of the unit Comm."
Ambient On/Off: this function, if enabled, allows the start-up and the shutdown of the unit through external
temperature. Enable the function under "User" password by entering the temperature value that will turn off the unit,
along with the differential temperature for re-start. In the case the function is enabled, "Off Amb. Lockout" will appear
on the status display of the unit.
On/Off Time Schedule: This function, if enabled, allows the start-up and the shutdown of the unit in accordance with a
user defined time schedule. Enable the function under "User" password by entering the start-up and shutdown time for
different weekdays and defining the holidays (forced-off days). In the case the function is enabled, "Off Time Schedule"
will appear on the status display of the unit.
Содержание
- Contents 2
- General description 2
- Main features of control software 4
- Components description 5
- Main board 6
- Eexv valve driver 7
- Addressing of plan 8
- Alarms that will shutdown the system 8
- Meaning of the eexv driver status leds 8
- Other alarms 8
- Air cooled chillers unit config 00 9
- Analogue inputs analogue inputs n compressor 1 compressor 2 compressor 3 compressor 4 9
- Controller input output 9
- Digital inputs 9
- N compressor 1 compressor 2 compressor 3 compressor 4 9
- Analogue inputs n compressor 1 compressor 2 compressor 3 compressor 4 10
- Analogue outputs n compressor 1 compressor 2 compressor 3 compressor 4 10
- Digital inputs n compressor 1 compressor 2 compressor 3 compressor 4 10
- Digital outputs n compressor 1 compressor 2 compressor 3 compressor 4 10
- Water cooled heat pump or pursuit unit config 01 or 02 10
- Analogue outputs n compressor 1 compressor 2 compressor 3 compressor 4 11
- Digital inputs 11
- Digital outputs n compressor 1 compressor 2 compressor 3 compressor 4 11
- N compressor 1 compressor 2 compressor 3 compressor 4 11
- Water cooled chillers unit config 03 11
- Analogue inputs n compressor 1 compressor 2 compressor 3 compressor 4 12
- Analogue outputs n compressor 1 compressor 2 compressor 3 compressor 4 12
- Digital analogue outputs n compressor 1 compressor 2 compressor 3 compressor 4 12
- Display and keypad 13
- General description 13
- Gg mm aa sat hh mm 13
- Unit status cooling staging xxx stp source local 13
- Keypad keys and their functions 14
- Category description keys password 15
- Main menu 15
- User menu 16
- Input output menu i o menu 17
- Manufacturer menu 17
- Setting menu 17
- Warning 17
- Maintenance menu 18
- Alarm list 19
- Alarms menu 19
- Buffer alarm menu 19
- Service menu 19
- Description of the compressor capacity control 20
- Setting of the capacity transducer 20
- Water temperature setpoint reset 20
- Soft load 21
- Start up inhibition 21
- Start up with high evaporator water temperature 21
- Unit limitation 21
- Appendix 1 software upload to the controller 22
- Dire c t upload from a pc 22
- Upload from programming key 23
- Appendix 2 unit start up sequence 24
- In the following paragraphs the unit start up management and shutdown procedures are shown in addition to this the compressors loading and unloading strategy is shown 24
- Unit startup and compressors management 24
- Appendix 3 plan settings 27
Похожие устройства
- Daikin EWWD700CJYNN Инструкция по монтажу
- Daikin EWWD700CJYNN Технические данные
- Daikin EWWD700CJYNN Сервис мануал
- Daikin EWWD750CJYNN Инструкция оператора
- Daikin EWWD750CJYNN Инструкция по монтажу
- Daikin EWWD750CJYNN Технические данные
- Daikin EWWD750CJYNN Сервис мануал
- Daikin EWWD800CJYNN Инструкция оператора
- Daikin EWWD800CJYNN Инструкция по монтажу
- Daikin EWWD800CJYNN Технические данные
- Daikin EWWD800CJYNN Сервис мануал
- Daikin EWWD900CJYNN Инструкция оператора
- Daikin EWWD900CJYNN Инструкция по монтажу
- Daikin EWWD900CJYNN Технические данные
- Daikin EWWD900CJYNN Сервис мануал
- Daikin EWWD950CJYNN Инструкция оператора
- Daikin EWWD950CJYNN Инструкция по монтажу
- Daikin EWWD950CJYNN Технические данные
- Daikin EWWD950CJYNN Сервис мануал
- Daikin EWWDC10CJYNN Инструкция оператора