Daikin EWWDC19CJYNN [4/28] Main features of control software
4
2. Main features of control software
• Management of water-cooled chillers.
• Control of the outlet temperature of evaporator, condenser, or both.
• Control of leaving water within ± 0.1 °C (under stable load conditions).
• Management of sudden load drops of up to 50% with max 3°C controlled temperature oscillation.
• Readout of all the main operating parameters of the unit (temperatures, pressures, etc.).
• Automatic control of primary evaporator and condenser pumps.
• Control of up to 4 steps of cooling tower plus regulation bypass valve with a proportional 0-10 Vdc signal.
• Dual setpoint through local or remote change-over switch. This function allows switching of the local setpoint
between two preset values.
• Setpoint override using an external (4-20 mA) signal –either outside ambient temperature or evaporator return
temperature.
• Adjustable Max Pull-Down rate reduces under-shoot during low demand in the control loop.
• Hot-water start feature allows the unit to start smoothly even under high temperature condition of evaporator
water.
• SoftLoad feature reduces electrical consumption and peak demand charges during loop low demand.
• Power-limiting feature reduces the electrical consumption of the unit by limiting either current (current limit) or
capacity demand (demand limit).
• Fan Quiet Mode feature helps reduce noise by limiting the speed of the fans in accordance with a time schedule
• Panel-mounted 15-key keypad for quick interfacing. The operator can log the chiller operating conditions on the
4-line by 20-column backlit display.
• Four levels of security protection against unauthorized changes.
• Compressor diagnostic system that includes logging of the last ten alarms and information on date, time and
current operating conditions at the time the alarm was activated.
• Weekly and yearly start-stop time schedule.
• Ambient Lockout feature allows the unit shutdown based on outside ambient temperature.
• Easy integration into building automation systems via separate 4-20 mA signals for chilled water temperature
setpoint and limitation of demand.
• Communication capabilities for remote monitoring, changing of setpoint, trend logging, alarm and event
detection, via compatible IBM-PC running monitoring software 2.0 or later.
• BMS communication capability via Modbus, LonWork, Johnson Metasys.
• Remote communication capabilities via modem (up to 8 chillers with Gateway Modem).
• Remote communication capabilities via GSM Modem.
Содержание
- Contents 2
- General description 2
- Main features of control software 4
- Components description 5
- Main board 6
- Eexv valve driver 7
- Addressing of plan 8
- Alarms that will shutdown the system 8
- Meaning of the eexv driver status leds 8
- Other alarms 8
- Air cooled chillers unit config 00 9
- Analogue inputs analogue inputs n compressor 1 compressor 2 compressor 3 compressor 4 9
- Controller input output 9
- Digital inputs 9
- N compressor 1 compressor 2 compressor 3 compressor 4 9
- Analogue inputs n compressor 1 compressor 2 compressor 3 compressor 4 10
- Analogue outputs n compressor 1 compressor 2 compressor 3 compressor 4 10
- Digital inputs n compressor 1 compressor 2 compressor 3 compressor 4 10
- Digital outputs n compressor 1 compressor 2 compressor 3 compressor 4 10
- Water cooled heat pump or pursuit unit config 01 or 02 10
- Analogue outputs n compressor 1 compressor 2 compressor 3 compressor 4 11
- Digital inputs 11
- Digital outputs n compressor 1 compressor 2 compressor 3 compressor 4 11
- N compressor 1 compressor 2 compressor 3 compressor 4 11
- Water cooled chillers unit config 03 11
- Analogue inputs n compressor 1 compressor 2 compressor 3 compressor 4 12
- Analogue outputs n compressor 1 compressor 2 compressor 3 compressor 4 12
- Digital analogue outputs n compressor 1 compressor 2 compressor 3 compressor 4 12
- Display and keypad 13
- General description 13
- Gg mm aa sat hh mm 13
- Unit status cooling staging xxx stp source local 13
- Keypad keys and their functions 14
- Category description keys password 15
- Main menu 15
- User menu 16
- Input output menu i o menu 17
- Manufacturer menu 17
- Setting menu 17
- Warning 17
- Maintenance menu 18
- Alarm list 19
- Alarms menu 19
- Buffer alarm menu 19
- Service menu 19
- Description of the compressor capacity control 20
- Setting of the capacity transducer 20
- Water temperature setpoint reset 20
- Soft load 21
- Start up inhibition 21
- Start up with high evaporator water temperature 21
- Unit limitation 21
- Appendix 1 software upload to the controller 22
- Dire c t upload from a pc 22
- Upload from programming key 23
- Appendix 2 unit start up sequence 24
- In the following paragraphs the unit start up management and shutdown procedures are shown in addition to this the compressors loading and unloading strategy is shown 24
- Unit startup and compressors management 24
- Appendix 3 plan settings 27
Похожие устройства
- Daikin EWWDC19CJYNN Инструкция по монтажу
- Daikin EWWDC19CJYNN Технические данные
- Daikin EWWDC19CJYNN Сервис мануал
- Daikin EUWAC5FZW Технические данные
- Daikin EUWAC5FZW Инструкция по эксплуатации
- Daikin EUWAC5FZW Сервис мануал
- Daikin EUWAC8FZW Технические данные
- Daikin EUWAC8FZW Инструкция по эксплуатации
- Daikin EUWAC8FZW Сервис мануал
- Daikin EUWAC10FZW Технические данные
- Daikin EUWAC10FZW Инструкция по эксплуатации
- Daikin EUWAC10FZW Сервис мануал
- HP Deskjet F2200 All-in-One Руководство по установке
- HP Deskjet F2200 All-in-One Основные сведения
- HP Deskjet F2200 All-in-One Руководство пользователя
- Xiaomi Mi AirDots Руководство пользователя
- Redmond RMC-М150 Руководство пользователя
- Makita UD2500 Руководство пользователя
- Panasonic ER407 Руководство пользователя
- Samsung UE43NU7100U Руководство пользователя