Daikin EWWDC19CJYNN [4/28] Main features of control software

4
2. Main features of control software
Management of water-cooled chillers.
Control of the outlet temperature of evaporator, condenser, or both.
Control of leaving water within ± 0.1 °C (under stable load conditions).
Management of sudden load drops of up to 50% with max 3°C controlled temperature oscillation.
Readout of all the main operating parameters of the unit (temperatures, pressures, etc.).
Automatic control of primary evaporator and condenser pumps.
Control of up to 4 steps of cooling tower plus regulation bypass valve with a proportional 0-10 Vdc signal.
Dual setpoint through local or remote change-over switch. This function allows switching of the local setpoint
between two preset values.
Setpoint override using an external (4-20 mA) signal –either outside ambient temperature or evaporator return
temperature.
Adjustable Max Pull-Down rate reduces under-shoot during low demand in the control loop.
Hot-water start feature allows the unit to start smoothly even under high temperature condition of evaporator
water.
SoftLoad feature reduces electrical consumption and peak demand charges during loop low demand.
Power-limiting feature reduces the electrical consumption of the unit by limiting either current (current limit) or
capacity demand (demand limit).
Fan Quiet Mode feature helps reduce noise by limiting the speed of the fans in accordance with a time schedule
Panel-mounted 15-key keypad for quick interfacing. The operator can log the chiller operating conditions on the
4-line by 20-column backlit display.
Four levels of security protection against unauthorized changes.
Compressor diagnostic system that includes logging of the last ten alarms and information on date, time and
current operating conditions at the time the alarm was activated.
Weekly and yearly start-stop time schedule.
Ambient Lockout feature allows the unit shutdown based on outside ambient temperature.
Easy integration into building automation systems via separate 4-20 mA signals for chilled water temperature
setpoint and limitation of demand.
Communication capabilities for remote monitoring, changing of setpoint, trend logging, alarm and event
detection, via compatible IBM-PC running monitoring software 2.0 or later.
BMS communication capability via Modbus, LonWork, Johnson Metasys.
Remote communication capabilities via modem (up to 8 chillers with Gateway Modem).
Remote communication capabilities via GSM Modem.