Daikin EWWDC19CJYNN [22/180] Electrical specifications ewwd cjynn

Daikin EWWD480CJYNN [22/180] Electrical specifications ewwd cjynn
General Outline ESIE07-05
1–6 Part 1 – System Outline
3
1
1
4
5
1.3 Electrical Specifications: EWWD-CJYNN
Note: 1 Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.(2)
2 Absorbed current referred to nominal condition: 12/7°C entering/leaving evaporator water
temperature; 30/35°C entering/leaving condenser water temperature.
3 Absorbed current referred to the following conditions: 14/9°C entering/leaving evaporator water
temperature; 50/55°C entering/leaving condenser water temperature.
4 Absorbed current of compressor n°1+(n°2)+(n°3) at nominal conditions+inrush current of last
compressor (n°4).
5 Compressor FLA (Full Load Ampere).
Model EWWD-CJYNN
Unit size 340 400 480 550 700 750 800
Standard voltage (1) 400 V - 3 ph - 50Hz
Nominal unit current (2) A 154 168 185 187 308 323 336
Max unit current (3) A 193 217 255 257 386 412 436
Max unit inrush current (4) A 593 593 593 593 709 719 725
Max unit current for wires sizing (5) A 230 260 320 320 460 490 520
Unit size 900 950 C10 C11 C12 C13
Standard voltage (1) 400 V - 3 ph - 50Hz
Nominal unit current (2) A 354 370 478 491 504 528
Max unit current (3) A 472 510 605 628 651 690
Max unit inrush current (4) A 732 738 835 841 845 858
Max unit current for wires sizing (5) A 580 640 720 750 780 840
Unit size C14 C15 C16 C17 C18 C19
Standard voltage (1) 400 V - 3 ph - 50Hz
Nominal unit current (2) A 543 561 648 676 706 736
Max unit current (3) A 729 768 824 872 944 1016
Max unit inrush current (4) A 865 871 961 71 997 1009
Max unit current for wires sizing (5) A 900 960 980 1040 1160 1280