Daikin EWAPC14AJYNN [19/41] Specifications

Daikin EWAPC11AJYNN [19/41] Specifications
3
1
3
Hydronic Systems • Chillers
19
Chillers • R-407C • EWAP-AJYNN
3 Specifications
3-2 ELECTRICAL SPECIFICATIONS
EWAP850AJYNN/A EWAP900AJYNN/A EWAP950AJYNN/A EWAPC10AJYNN/A EWAPC11AJYNN/A EWAPC12AJYNN/A
Power Supply Name YN
Phase 333333
Frequency Hz 50 50 50 50 50 50
Voltage V 400 400 400 400 400 400
Voltage
Tolerance
Minimum % -10%
Maximum % +10%
Unit Starting Current A 1051 1055 1125 1129 1172 1259
Nominal Running Current
Cooling
A 477 523 652 707 757 710
Maximum Running Current A 660 723 782 853 920 984
Max unit current for wires
sizing
A 684 744 804 864 924 1026
FanPhase 333333
Voltage V 400 400 400 400 400 400
Nominal Running Current
Cooling
A646872768096
CompressorPhase 333333
Voltage V 400 400 400 400 400 400
Voltage
Tolerance
Minimum % -10%
Maximum % +10%
Maximum Running Current A 596 655 710 777 840 888
Starting Method Star-delta
Notes Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
Max unit starting current: Starting current of biggest compressor + 75% of nominal absorbed current of the other
compressor + fans current.
Max unit current for wires sizing : compressor FLA (Full Load Ampere) + fans current.
3-2 ELECTRICAL SPECIFICATIONS
EWAPC13AJYNN/A EWAPC14AJYNN/A EWAPC15AJYNN/A EWAPC16AJYNN/A EWAPC17AJYNN/A EWAPC18AJYNN/A
Power Supply Name YN
Phase 333333
Frequency Hz 50 50 50 50 50 50
Voltage V 400 400 400 400 400 400
Voltage
Tolerance
Minimum % -10%
Maximum % +10%
Unit Starting Current A 1232 1332 1406 1407 1486 1489
Nominal Running Current
Cooling
A 756 796 972 1023 1078 1121
Maximum Running Current A 1048 1106 1168 1235 1296 1365
Max unit current for wires
sizing
A 1086 1146 1210 1266 1322 1386
FanPhase 333333
Voltage V 400 400 400 400 400 400
Nominal Running Current
Cooling
A 100 104 112 112 112 120
CompressorPhase 333333
Voltage V 400 400 400 400 400 400
Voltage
Tolerance
Minimum % -10%
Maximum % +10%
Maximum Running Current A 948 1002 1056 1123 1184 1245
Starting Method Star-delta
Notes Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
Max unit starting current: Starting current of biggest compressor + 75% of nominal absorbed current of the other
compressor + fans current.
Max unit current for wires sizing : compressor FLA (Full Load Ampere) + fans current.