Daikin EWTP140MBYN Сервис мануал онлайн [219/452] 525507

Daikin EWWD240MBYNN Сервис мануал онлайн [219/452] 402624
ESIE05-07 Functional Control for a Standalone Unit
Part 2 – Functional Description 2–23
3
2
4
5
1
Line 4.1: For outlet water control
Line 4.2: For inlet water control
Line n° Display Description
Default (Depending
on control mode)
Lower
limit
Upper
limit
Unity
1 THERMOST.
SETTINGS
screen title
2
3
4.1 LOADUP
- DOWN
Sampling time to
loadup or -down
12 S
12 S
12 S
12 S
300 S
300 S
12 S
12 S
4.2 LOADUP
- DOWN
Sampling time to
loadup or -down
48 S
24 S
12 S
12 S
300 S
300 S
12 S
12 S
Line n° Display Description
Default (Depending
on control mode)
Lower
limit
Upper
limit
1 Service Menu Screen Title
2
3A:
B:
C:
Thermostat
setting A/B/C
0.8
0.5
0.2
0.8
0.5
0.2
6.0
1
0.4
4 INLDIFF Inlet water check
that allows
restart of unit
only if inlet water
temp rises with
0.5°C
Y
0.5
N
0.3
Y
2
ESIE05-07.book Page 23 Wednesday, October 11, 2006 10:42 AM