Daikin EWAP280MBYNN [222/452] Freeze up control

Daikin EWAP400MBYN [222/452] Freeze up control
Functional Control for a Standalone Unit ESIE05-07
2–26 Part 2 – Functional Description
3
1
2
4
5
2.6 Freeze-up Control
Introduction Freeze-up control is used to protect the evaporator against accidentally freezing.
Two protections are present: freeze-up prevention and freeze-up protection.
However this function is not applicable on evaporator-less units.
Applicable units
Freeze-up
prevention
Freeze-up prevention will request a load-down when the temperature of the evaporator outlet water
gets 0.5°C below the minimum outlet water (MOW) temperature. This activates the freeze-up timer if
after the sampling time the temperature is still too low another load-down will be requested. When the
temperature rises above the MOW temperature again the freeze-up prevention is reset and the unit
will work in its initial mode. The compressor will go back to the necessary capacity, depending on the
load-up possible status.
When freeze-up prevention is active the compressor status in the readout menu is blinking: "ON - XX%
DELTA".
Air-cooled
cooling only
Evaporator-less Water-cooled
unit
Condenser-less
unit
EWAD EWAP EWTP ERAP EWWD EWLD
CO CO HR CA HP RC
Freeze-up
prevention
XXX X X
Characteristics Freeze up prevention
Control device Sensor
Diagram name R3T, R4T
Activation
Result
Outlet water temperature < M.O.W.-0.5K
Load-down of 10 sec each sampling time
(default 12 sec)
Reset
Result
Outlet water temperature > M.O.W.
Normal mode
ESIE05-07.book Page 26 Wednesday, October 11, 2006 10:42 AM