Daikin EWAP280MBYNN [23/452] Model ewld 120mbynn ewld 170mbynn ewld 240mbynn ewld 260mbynn ewld 340mbynn ewld 400mbynn ewld 480mbynn ewld 500mbynn ewld 540mbynn

Daikin EWAP400MBYN [23/452] Model ewld 120mbynn ewld 170mbynn ewld 240mbynn ewld 260mbynn ewld 340mbynn ewld 400mbynn ewld 480mbynn ewld 500mbynn ewld 540mbynn
ESIE 05-07 General Outline
Part 1 – System Outline 1–11
3
1
4
5
Notes 1. Nominal cooling capacity at Eurovent conditions: Entering/Leaving water evaporator = 12°C/7°C;
Condensing temperature = 45°C.
2. Nominal power input at Eurovent conditions: See Eurovent 6/C/003 Entering/Leaving water
temperature = 12°C/7°C; Condensing temperature = 45°C.
3. Min. required water volume for standard thermostat settings and at nominal conditions.
4. Piping connections are delivered with victaulic joint and counterpipe for welding.
5. Dimension values between brackets include installation space of delivered filter.
Weight
Machine
weight
891 kg 1110 kg 1342 kg 1428 kg 2220 kg 2452 kg 2684 kg 2770 kg 2858 kg
Operation
weight
907 kg 1130 kg 1369 kg 1462 kg 2260 kg 2497 kg 2738 kg 2831 kg 2924 kg
Casing
Colour
Ivory white / Munsell code 5Y7.5/1 / ± RAL 7044
Material
Polyester coated galvanised steel plate
Sound
power
level
91 dBA 95 dBA 96 dBA 98 dBA 99 dBA
Safety
devices
Q Double PED approved high pressure switches
Q Low pressure protection
Q Pressure relief valve
Q Compressor motor thermal protector
Q Compressor motor overcurrent relay
Q Discharge temperature protector
Q Freeze up protection
Q Recycling and quard timer
Q Reverse phase protector/flow switch
Model
EWLD
120MBYNN
EWLD
170MBYNN
EWLD
240MBYNN
EWLD
260MBYNN
EWLD
340MBYNN
EWLD
400MBYNN
EWLD
480MBYNN
EWLD
500MBYNN
EWLD
540MBYNN
ESIE05-07.book Page 11 Wednesday, October 11, 2006 10:42 AM