Daikin EWAD380MBYNN [366/452] Overview of network safeties
Overview of Fault Indications and Safeties ESIE05-07
3–10 Part 3 – Troubleshooting
3
1
3
4
5
1.6 Overview of Network Safeties
Network safeties
Code&display
NETWORK SAFETY
Description
Safety possible
if unit is off?
1. PCB Commun.
Problem
0U4: PCB COMM.PROB-
LEM
1 Only if MSOptionSetting = yes!
2 On every unit for which the status of the
pLAN is not OK.
3 On master: If not all slaves are found (also
possible if MSOptionSetting =no on a slave)
4 On slaves: If no master unit is found.
5 On slaves: If slave is not integrated in Master
(ex nr of slaves 1 then error on slave 2)
This safety is only enabled if the error is
pressent for 120 sec. (default)
(Only possible if a network of different control-
lers exists)
Y
2. Outlet Evapora-
tor sensor error
0CA: OUT E SENSOR ERR 1 Only if MSOptionSetting = yes!
2 Only on master
Sensor out of range, broken, bad contact,...
read-out for sensor (AI3) is +Er / -Er
(Only if ChaAI1=MS mixed outlet sensor)
Y
3. Inlet evaporator
sensor error
0C9: INL E SENSOR ERR 1 Only if MSOptionSetting = yes!
2 Only on master
Sensor out of range, broken, bad contact,...
read-out for sensor (AI4) is +Er / -Er
Y