R134a

R407C



Economiser motor
protection

!"
"!##
set point
60,0°C 60,0°C 0-999,9
diff.
5,0°C 5,0°C 0-99,9
Temperature regulation
Integral time
200 200 0-999
Derivative time
60 60 1-999
Compressor
configuration
Number of compressors
2 2 1-4
Number of evaporators
1 1 1-2

$#
# > 2
Min. time interval before
any given compressor
is allowed to re-start
600 600 0-999
Min. time interval
between running
periods of any two
compressors
120 120 0-999
Min running time for
compressors
120 120 0-999
Min stop time for
compressors
180 180 0-999
Interstage 210 210 1-999
Double pulse under
35% 35% 0-100
P.hold Cond 17,5 % 26,5 % -1-50
P.down Cond 18,5 % 27,5 % -1-50
P.hold Evap 1,9 % 3,6 % -1-50
P.down Evap 1,8 % 3,4 % -1-50
Alarm setpoint for high
discharge temperature
110 °C 110 °C 0-140.0
Flow switch alarm delay
start
20 20 0-99
run
5 5 0-99
Freeze prevent
setpoint
--------
3,0 °C 3,0 °C -99,9-99,9
diff.
1,0 °C 1,0 °C -99,9-99,9
Antifreeze alarm
setpoint
--------
2,0 °C 2,0 °C -99,9-99,9
diff.
1,0 °C 1,0 °C -99,9-99,9
Evap 1 antifreeze alarm
# 2

setpoint
--------
2,0 °C 2,0 °C -99,9-99,9
diff.
1,0 °C 1,0 °C -99,9-99,9

Содержание

Хладагент R134a Параметр Хладагент R407C Допустимый диапазон Примечания Только если экономайзер задействован Economiser motor protection set point diff Temperature regulation Integral time Derivative time Compressor configuration Number of compressors Number of evaporators Min time interval before any given compressor is allowed to re start Min time interval between running periods of any two compressors Min running time for compressors Min stop time for compressors Interstage Double pulse under P hold Cond P down Cond P hold Evap P down Evap Alarm setpoint for high discharge temperature Flow switch alarm delay start run Freeze prevent setpoint diff 60 0 C 5 0 C 60 0 С 5 0 C 0 999 9 0 99 9 200 c 60 c 200 с 60 с 0 999 1 999 2 2 1 4 1 1 1 2 600 c 600 с 0 999 120 c 120 с 0 999 120 c 120 с 0 999 180 c 180 с 0 999 210 c 35 17 5 бара 18 5 бара 1 9 бара 1 8 бара 210 с 35 26 5 бара 27 5 бара 3 6 бара 3 4 бара 1 999 0 100 1 50 1 50 1 50 1 50 110 C 110 C 0 140 0 20 с 5с 20 с 5с 0 99 0 99 3 0 C 3 0 C 99 9 99 9 1 0 C 1 0 C 99 9 99 9 2 0 C 2 0 C 99 9 99 9 1 0 C 1 0 C 99 9 99 9 Только если количество компрессоров 2 Antifreeze alarm setpoint diff Только для агрегатов с 2 испарителями Evap 1 antifreeze alarm setpoint diff 2 0 C 2 0 C 99 9 99 9 1 0 C 1 0 C 99 9 99 9 24