Daikin EWADC15BJYNN [28/52] Диапазон примечания

Daikin EWADC15BJYNN [28/52] Диапазон примечания
28


R134a

R407C



EXV settings
Valve type ALCO EX8, ALCO EX8,
ALCO EX5-EX6,
ALCO EX7,
ALCO EX8,
SPORLAND SEI 0.5-11,
SPORLAND SEI 25,
SPORLAND SEH 50-
250,
DANFOSS ETS50,
DANFOSS ETS100,
DANFOSS X,
CAREL E2V,
CAREL NEW,
!!"#$
SEH 50-250
gas type R134A R407C R22
R134a
R404a
R407c
R410a
R507c
R290
R600
R600a
R717
R744
EXVs settings
Opening extra steps Y Y Y/N
Closing extra steps Y Y Y/N
Time extra steps 0 0 0-9999
EXV settings
SH (superheat) setpoint
6,0 °C 6,0 °C 0-50,0
dead band 0,0 °C 0,0 °C 0-9,9
EXV settings % SHE 50-250
Prop. Factor 80,0 80,0 0-99,9 35
Integral factor 30 30 0-999 30
Differential factor 0,5 0,5 0-99, 1
EXV settings
Low SH protection
setpoint 1,0 °C 1,0 °C -4,0-21,0
integral time 1 1 0-300
EXV settings
LOP protection
setpoint -30 °C -30 °C -50,0-70,0
integral time 4,0 4,0 0-60,0
EXV settings
MOP protection
setpoint 12,0 12,0 -50-70
integral time 4,0 4,0 0-99,9
EXV settings
MOP protection
startup delay 90 90 0-600

Содержание

Параметр EXV settings Valve type Хладагент R134a ALCO EX8 Хладагент R407C ALCO EX8 Допустимый диапазон ALCO EX5 EX6 ALCO EX7 ALCO EX8 SPORLAND SEI 0 5 11 SPORLAND SEI 25 SPORLAND SEH 50250 DANFOSS ETS50 DANFOSS ETS100 DANFOSS X CAREL E2V CAREL NEW ОСОБЫЙ R134A R407C R22 R 134a R404a R407c R410a R507c R290 R600 R600a R717 R744 Y Y Oc Y Y 0c Y N Y N 0 9999 6 0 C 0 0 C 6 0 C 0 0 C 0 50 0 0 9 9 80 0 30 c 0 5 c 80 0 30 c 0 5 c 0 99 9 0 999 0 99 1 0 C 1c 1 0 C 1c 4 0 21 0 0 300 setpoint integral time EXV settings MOP protection 30 C 4 0 c 30 C 4 0 c 50 0 70 0 0 60 0 setpoint integral time EXV settings MOP protection 12 0c 4 0 c 12 0c 4 0 c 50 70 c 0 99 9 c startup delay 90 c 90 c 0 600 c gas type EXVs settings Opening extra steps Closing extra steps Time extra steps EXV settings SH superheat setpoint dead band EXV settings Prop Factor Integral factor Differential factor EXV settings Low SH protection setpoint integral time Примечания SEH 50 250 Для SHE 50 250 35 30 1 EXV settings LOP protection 28