Daikin EWYP110CAYN [6/43] Specifications

Daikin EWYP095CAYN [6/43] Specifications
3
1
2
Hydronic Systems
Chillers
6
Chillers
R-407C
2 Specifications
2-2 ELECTRICAL SPECIFICATIONS EWYP060CAYN EWYP075CAYN EWYP095CAYN EWYP110CAYN EWYP120CAYN EWYP130CAYN
Power Supply Phase 3
Frequency Hz 50
Voltage V 400
Voltage
Tolerance
Minimum % -10%
Maximum % +10%
Unit Starting Current A 203 215 237 327 336 259
Starting current soft start A 133 145
Nominal Running Current
Cooling
A 57 68 90 102 111 112
Maximum Running Current A 60.8 72.9 97.2 109.2 120.2 119.3
Recommended fuses according to
IEC standard 269-2
80 80 100 125 125 125
Fan Type Standard
Quantity 2 3 3 3 3 4
Phase 3 3 3 3 3 3
Voltage V 400 400 400 400 400 400
Nominal Running Current
Cooling
A 1.5 1.5 2.4 2.4 2.4 1.5
Maximum Running Current A 1.8 1.8 2.9 2.9 2.9 1.8
Starting current (MSC) A 6.7 6.7 10.8 10.8 10.8 6.7
Type Hi-ESP (OPHF)
Quantity 2 3 3 3 3 4
Phase 3 3 3 3 3 3
Voltage V 400 400 400 400 400 400
Nominal Running Current
Cooling
A 2.55 2.55 5.7 5.7 5.7 2.55
Maximum Running Current A 2.9 2.9 6.3 6.3 6.3 2.9
Starting current (MSC) A 11.5 11.5 28.3 28.3 28.3 11.5
Pump Type Single
Phase 3 3 3 3 3 3
Power input kW 1.85 1.85 1.85 4 4 4
Speed rpm 2900 2900 2900 2900 2900 2900
Voltage V 400 400 400 400 400 400
Maximum Running Current A 4.95 4.95 4.95 7.5 7.5 7.5
Type Twin (OPTP)
Phase 3 3 3 3 3 3
Power input kW 2.2 2.2 2.2 4 4 4
Speed rpm 2900 2900 2900 2900 2900 2900
Voltage V 400 400 400 400 400 400
Maximum Running Current A 4.9 4.9 4.9 7.5 7.5 7.5
Compressor Phase 3
Voltage V 400
Voltage
Tolerance
Minimum % -10%
Maximum % +10%
Starting current A 175 175 175 272 272 175
Nominal running current
(RLA)
A 19+28.5 28.5+28.5 28.5+28.5+19 38+47 47+47 2x(19+28.5)
Maximum Running Current A 52.3 62.6 83.6 93 104 104.6
Power factor 0.85 0.85 0.85 0.87 0.87 0.85
Starting Method Direct on line
Recommended fuses 80 80 100 125 125 125
Control Circuit Phase 1 1 1 1 1 1
Voltage V 230+24
Recommended fuses 6 + 2
Crankcase heater (E1/2HC) W 160 160 160 150 150 160