2 Specifications
2-2 ELECTRICAL SPECIFICATIONS EWYP150CAYN EWYP170CAYN EWYP200CAYN EWYP220CAYN EWYP250CAYN
Power Supply Phase 3
Frequency Hz 50
Voltage V 400
Voltage
Tolerance
Minimum % -10%
Maximum % +10%
Unit Starting Current A 282 300 335 356 450
Nominal Running Current
Cooling
A 135 154 188 209 226
Maximum Running Current A 143.5 164.9 203.5 227.7 247.9
Recommended fuses according to
IEC standard 269-2
160 200 250 250 250
Fan Type Standard
Quantity 6 6 6 6 6
Phase 3 3 3 3 3
Voltage V 400 400 400 400 400
Nominal Running Current
Cooling
A 1.5 1.5 4 4 4
Maximum Running Current A 1.8 1.8 4.8 4.8 4.8
Starting current (MSC) A 6.7 6.7 18 18 18
Type Hi-ESP (OPHF)
Quantity 6 6 6 6 6
Phase 3 3 3 3 3
Voltage V 400 400 400 400 400
Nominal Running Current
Cooling
A 2.55 2.55 5.7 5.7 5.7
Maximum Running Current A 2.9 2.9 6.3 6.3 6.3
Starting current (MSC) A 11.5 11.5 28.3 28.3 28.3
Pump Type Single
Phase 3 3 3 3 3
Power input kW 4 4 4 5.5 5.5
Speed rpm 2900 2900 2900 2900 2900
Voltage V 400 400 400 400 400
Maximum Running Current A 7.5 7.5 7.5 11.1 11.1
Type Twin (OPTP)
Phase 3 3 3 3 3
Power input kW 4 4 4 5.5 5.5
Speed rpm 2900 2900 2900 2900 2900
Voltage V 400 400 400 400 400
Maximum Running Current A 7.5 7.5 7.5 11.1 11.1
Compressor Phase 3
Voltage V 400
Voltage
Tolerance
Minimum % -10%
Maximum % +10%
Starting current A 175 175 175 175 272
Nominal running current
(RLA)
A 2x(28.5+28.5) 2x(19+19+28.5) 2x(28.5+28.5+19) 2x(28.5+28.5+28.5) 2x(47+47)
Maximum Running Current A 125.2 146.6 167.2 187.8 208
Power factor 0.85 0.85 0.85 0.85 0.87
Starting Method Direct on line
Recommended fuses 160 200 250 250 250
Control Circuit Phase 1 1 1 1 1
Voltage V 230+24
Recommended fuses 6 + 2
Crankcase heater (E1/2HC) W 160 160 160 160 160