Daikin EWAQ230F-SS [13/67] Technical specifications

Daikin EWAQ400F-XS [13/67] Ewaq f sr
TECHNICAL SPECIFICATIONS
EWAQ F-SR
460
530
580
380
MODEL
Capacity - Cooling (1) kW 580 456 383 527
Capacity control - Type
---
Step
Step
Step
Step
Capacity control - Minimum capacity % 17.0 17.0 25.0 14.0
Unit power input - Cooling (1)
kW
233
191
159
208
EER (1)
---
2.49
2.39
2.41
2.53
ESEER --- 4.33 4.49 4.15 4.42
IPLV
---
4.81
5.04
4.72
4.91
CASING
Colour (2)
---
IW
IW
IW
IW
Material (2) --- GPSS GPSS GPSS GPSS
DIMENSIONS
Height
mm
2221
2221
2397
2221
Width mm 2258 2258 2258 2258
Length
mm
5010
4110
3210
5010
WEIGHT
Unit Weight
kg
4108
3481
3216
3863
Operating Weight kg 4154 3527 3256 3909
WATER HEAT EXCHANGER
Type (3)
---
PHE
PHE
PHE
PHE
Water Volume l 46 46 40 46
Nominal water flow rate - Cooling
l/s
27.8
21.8
18.3
25.2
Nominal Water pressure drop - Cooling kPa 51 31 29 42
Insulation material (4)
CC
CC
CC
CC
AIR HEAT EXCHANGER
Type (5) --- HFP HFP HFP HFP
FAN
Type (6) --- DPT DPT DPT DPT
Drive (7)
---
DOL
DOL
DOL
DOL
Diameter mm 800 800 800 800
Nominal air flow
l/s
40713
33487
24922
41858
Quantity
No.
10
8
6
10
Speed rpm 705 705 705 705
Motor input
kW
7.5
6.0
4.5
7.5
COMPRESSOR
Type
---
Scroll
Scroll
Scroll
Scroll
Oil charge l 38 38 25 38
Quantity No. 6 6 4 6
SOUND LEVEL
Sound Power - Cooling dB(A) 92 89 90 91
Sound Pressure - Cooling (8)
dB(A)
72
70
71
71
REFRIGERANT CIRCUIT
Refrigerant type
---
R410A
R410A
R410A
R410A
Refrigerant charge kg 46 34 24 40
N. of circuits No. 2 2 2 2
PIPING CONNECTIONS
Evaporator water inlet/outlet 3" 3" 3" 3"
Fluid: Water
(1) Cooling capacity, unit power input in cooling and EER are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load
operation;
(2) IW: Ivory White; GPSS: Galvanized and Painted Steel Sheet; (3) PHE: Plate Heat Exchanger --- S&T: Single Pass Shell & Tube
(4) CC: Closed Cell; (5) HFP: High efficiency fin and tube type with integral subcooler
(6) DPT: Direct Propeller Type; (7) DOL: Direct On Line - VFD: Inverter - BRS: Brushless
(8) The values are according to ISO 3744 and are referred to: evaporator 12/7°C, ambient 35°C, full load operation.
Pagina 13 di 67