Daikin EWAQ230F-SS [44/67] Cooling performance

Daikin EWAQ320F-SL [44/67] Cooling performance
COOLING PERFORMANCE
EWAQ F-XS
610
680
43
40
35
30
25
46
43
40
35
30
25
46
Ta
Twout
CC
kW
5
642
610
575
537
513
488
710
675
637
597
571
544
PI
kW
166
179
194
212
224
236
186
200
216
234
246
260
qw
l/s
30.7
29.2
27.5
25.7
24.5
23.3
34.0
32.3
30.5
28.6
27.3
26.0
dpw
kPa
49
44
40
35
32
28
62
56
50
43
40
36
CC
kW
7
677
643
607
567
542
516
749
712
672
630
603
575
PI
kW
169
182
198
215
227
239
190
203
219
237
250
263
qw
l/s
32.4
30.8
29.0
27.2
25.9
24.7
35.9
34.1
32.2
30.2
28.9
27.5
dpw
kPa
55
50
44
39
35
32
69
62
55
49
44
40
CC
kW
9
713
677
639
598
572
544
788
750
708
664
636
606
PI
kW
172
186
201
218
230
243
193
207
223
241
253
266
qw
l/s
34.2
32.5
30.6
28.6
27.4
26.1
37.9
36.0
34.0
31.8
30.5
29.1
dpw
kPa
61
55
49
43
39
36
76
69
61
54
49
45
CC
kW
11
750
712
672
629
602
573
829
788
745
698
669
638
PI
kW
176
189
204
222
233
246
197
210
226
244
256
269
qw
l/s
36.0
34.2
32.2
30.2
28.8
27.5
39.9
37.9
35.8
33.5
32.1
30.6
dpw
kPa
68
61
54
48
44
39
85
76
68
60
55
50
CC
kW
13
788
748
706
660
632
602
871
828
783
734
703
671
PI
kW
179
193
208
225
237
250
200
214
230
248
260
273
qw
l/s
37.9
35.9
33.9
31.7
30.3
28.9
41.9
39.9
37.6
35.3
33.8
32.2
dpw
kPa
75
68
60
53
48
44
94
85
75
66
61
55
CC
kW
15
826
785
740
693
663
548
914
869
822
770
738
705
PI
kW
183
196
212
229
241
201
204
218
233
251
263
276
qw
l/s
39.8
37.8
35.6
33.3
31.9
26.3
44.1
41.9
39.6
37.1
35.5
33.9
dpw
kPa
83
74
66
58
53
36
103
93
83
73
67
61
Fluid: Water
Ta: Condenser inlet air temperature; Twout: Evaporator leaving water temperature (Δt 5°C)
CC: Cooling capacity; PI: Power input; qw: Fluid flow rate; dpw: Fluid pressure drop
* For working condition where dpw value is "Italic-Red Color" please contac factory