ELECTRICAL SPECIFICATIONS
EWAQ F-XR
190 210 240 300 330 340 310 170 MODEL
POWER SUPPLY
Phases Nr 3 3 3 3 3 3 3 3
Frequency
Hz
50
50
50
50
50
50
50
50
Voltage V 400 400 400 400 400 400 400 400
Voltage tolerance Minimum % -10% -10% -10% -10% -10% -10% -10% -10%
Voltage tolerance Maximum
%
+10%
+10%
+10%
+10%
+10%
+10%
+10%
+10%
UNIT
Maximum starting current A 276 332 346 401 472 501 472 501
Nominal running current cooling
A
107
116
125
139
180
204
180
204
Mximum running current
A
132
143
157
173
220
249
220
249
Maximum current for wires sizing A 145 158 173 190 242 274 242 274
FANS
Nominal running current cooling
A
10
10
13
13
16
16
16
16
COMPRESSORS
Phases Nr 3 3 3 3 3 3 3 3
Voltage V 400 400 400 400 400 400 400 400
Voltage tolerance Minimum
%
-10%
-10%
-10%
-10%
-10%
-10%
-10%
-10%
Voltage tolerance Maximum % +10% +10% +10% +10% +10% +10% +10% +10%
Maximum running current
A
61
61
66
66
72
72
80
80
102
102
117
117
102
102
117
117
Starting method --- DOL DOL DOL DOL DOL DOL DOL DOL
EWAQ F-XR
410
430
500
580
650
390
MODEL
POWER SUPPLY
Phases
Nr
3
3
3
3
3
3
Frequency
Hz
50
50
50
50
50
50
Voltage V 400 400 400 400 400 400
Voltage tolerance Minimum
%
-10%
-10%
-10%
-10%
-10%
-10%
Voltage tolerance Maximum % +10% +10% +10% +10% +10% +10%
UNIT
Maximum starting current A 618 632 646 628 754 801
Nominal running current cooling
A
226
239
255
300
347
380
Mximum running current A 283 296 310 377 419 465
Maximum current for wires sizing
A
311
326
341
415
460
512
FANS
Nominal running current cooling
A
21
21
21
26
26
31
COMPRESSORS
Phases Nr 3 3 3 3 3 3
Voltage
V
400
400
400
400
400
400
Voltage tolerance Minimum % -10% -10% -10% -10% -10% -10%
Voltage tolerance Maximum % +10% +10% +10% +10% +10% +10%
Maximum running current A
131
131
131
145
145
145
175
175
189
203
217
217
Starting method --- DOL DOL DOL DOL DOL DOL
Fluid: Water
Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load
Nominal current in cooling mode is referred to the following conditions: evaporator 12/7°C; ambient 35°C; compressors + fans current.
Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current
Maximum unit current for wires sizing is based on minimum allowed voltage
Maximum current for wires sizing: (compressors full load ampere + fans current) x 1,1.
Pagina 25 di 67
Содержание
- Ewaq f p.1
- Databook p.1
- Performance according to en14511 p.1
- Air cooled scroll chillers p.1
- Certifications p.2
- Versions p.2
- Low operating cost and extended operating life p.2
- Superior control logic p.2
- Sound configurations p.2
- Pagina 2 di 67 p.2
- Outstanding reliability p.2
- Low operating sound levels p.2
- Features and benefits p.2
- Code requirements safety and observant of laws directives p.2
- Evaporator plate heat exchanger p.3
- Compressor p.3
- Cabinet and structure p.3
- General characteristics p.3
- Refrigerant circuit p.3
- Refrigerant p.3
- Pagina 3 di 67 p.3
- Electronic expansion valve p.3
- Electrical control panel p.3
- Condenser fans ø 800 p.3
- Condenser p.3
- Supervising systems on request p.4
- Pagina 4 di 67 p.4
- General characteristics p.4
- Standard options supplied on basic unit p.5
- Pagina 5 di 67 p.5
- Options on request p.5
- Options p.5
- Pagina 6 di 67 p.6
- Options p.6
- Sound level p.7
- Refrigerant p.7
- Pagina 7 di 67 p.7
- Nomenclature p.7
- Model series p.7
- Machine type p.7
- Inverter p.7
- Efficiency level p.7
- Capacity class in kw cooling p.7
- Technical specifications p.8
- Pagina 8 di 67 p.8
- Ewaq f ss p.8
- Pagina 9 di 67 p.9
- Ewaq f ss p.9
- Technical specifications p.9
- Technical specifications p.10
- Pagina 10 di 67 p.10
- Ewaq f sl p.10
- Ewaq f sl p.11
- Technical specifications p.11
- Pagina 11 di 67 p.11
- Technical specifications p.12
- Pagina 12 di 67 p.12
- Ewaq f sr p.12
- Technical specifications p.13
- Pagina 13 di 67 p.13
- Ewaq f sr p.13
- Technical specifications p.14
- Pagina 14 di 67 p.14
- Ewaq f xs p.14
- Technical specifications p.15
- Pagina 15 di 67 p.15
- Ewaq f xs p.15
- Technical specifications p.16
- Pagina 16 di 67 p.16
- Ewaq f xl p.16
- Technical specifications p.17
- Pagina 17 di 67 p.17
- Ewaq f xl p.17
- Technical specifications p.18
- Pagina 18 di 67 p.18
- Ewaq f xr p.18
- Technical specifications p.19
- Pagina 19 di 67 p.19
- Ewaq f xr p.19
- Electrical specifications p.20
- Pagina 20 di 67 p.20
- Ewaq f ss p.20
- Pagina 21 di 67 p.21
- Ewaq f sl p.21
- Electrical specifications p.21
- Pagina 22 di 67 p.22
- Ewaq f sr p.22
- Electrical specifications p.22
- Pagina 23 di 67 p.23
- Ewaq f xs p.23
- Electrical specifications p.23
- Pagina 24 di 67 p.24
- Ewaq f xl p.24
- Electrical specifications p.24
- Ewaq f xr p.25
- Electrical specifications p.25
- Pagina 25 di 67 p.25
- Sound levels p.26
- Pagina 26 di 67 p.26
- Ewaq f ss p.26
- Ewaq f sr p.26
- Ewaq f sl p.26
- Sound levels p.27
- Pagina 27 di 67 p.27
- Ewaq f xs p.27
- Ewaq f xr p.27
- Ewaq f xl p.27
- Table 2 water heat exchanger fouling factors p.28
- Table 1 water heat exchanger minimum and maximum water δt p.28
- Pagina 28 di 67 p.28
- Operating limits p.28
- Operating limits p.29
- Table 5 available fan static pressure correction factors p.29
- Table 4 minimum glycol percentage for low air ambient temperature p.29
- Table 3 air heat exchanger altitude correction factors p.29
- Pagina 29 di 67 p.29
- Water content in cooling circuits p.30
- Water charge flow and quality p.30
- Pagina 30 di 67 p.30
- Operating limits p.30
- Pagina 32 di 67 p.32
- Ewaq f ss p.32
- Cooling performance p.32
- Pagina 33 di 67 p.33
- Ewaq f ss p.33
- Cooling performance p.33
- Ewaq f ss p.34
- Cooling performance p.34
- Pagina 34 di 67 p.34
- Pagina 35 di 67 p.35
- Ewaq f sl p.35
- Cooling performance p.35
- Pagina 36 di 67 p.36
- Ewaq f sl p.36
- Cooling performance p.36
- Pagina 37 di 67 p.37
- Ewaq f sl p.37
- Cooling performance p.37
- Pagina 38 di 67 p.38
- Ewaq f sr p.38
- Cooling performance p.38
- Pagina 39 di 67 p.39
- Ewaq f sr p.39
- Cooling performance p.39
- Pagina 40 di 67 p.40
- Ewaq f sr p.40
- Cooling performance p.40
- Pagina 41 di 67 p.41
- Ewaq f xs p.41
- Cooling performance p.41
- Pagina 42 di 67 p.42
- Ewaq f xs p.42
- Cooling performance p.42
- Pagina 43 di 67 p.43
- Ewaq f xs p.43
- Cooling performance p.43
- Pagina 44 di 67 p.44
- Ewaq f xs p.44
- Cooling performance p.44
- Cooling performance p.45
- Pagina 45 di 67 p.45
- Ewaq f xl p.45
- Pagina 46 di 67 p.46
- Ewaq f xl p.46
- Cooling performance p.46
- Pagina 47 di 67 p.47
- Ewaq f xl p.47
- Cooling performance p.47
- Pagina 48 di 67 p.48
- Ewaq f xl p.48
- Cooling performance p.48
- Pagina 49 di 67 p.49
- Ewaq f xr p.49
- Cooling performance p.49
- Ewaq f xr p.50
- Cooling performance p.50
- Pagina 50 di 67 p.50
- Pagina 51 di 67 p.51
- Ewaq f xr p.51
- Cooling performance p.51
- Pagina 52 di 67 p.52
- Ewaq f xr p.52
- Cooling performance p.52
- Water pump kit p.53
- Single pump 2 poles p.53
- Pagina 53 di 67 p.53
- Options technical data p.53
- Water pump kit combination matrix p.54
- Twin pump 2 poles p.54
- Pagina 54 di 67 p.54
- Options technical data p.54
- Options technical data p.55
- Water pump kit technical information p.56
- Pagina 56 di 67 p.56
- Options technical data p.56
- Pagina 57 di 67 p.57
- Legend p.57
- Dimensional drawing p.57
- Compressor evaporator condenser coil electrical panel fan evaporator water inlet evaporator water outlet slot for power and control panel connection p.57
- A m l i h g b c f e d p.57
- 2 3 4 5 6 7 8 p.57
- Pagina 58 di 67 p.58
- Legend p.58
- Dimensional drawing p.58
- Compressor evaporator condenser coil electrical panel fan evaporator water inlet evaporator water outlet slot for power and control panel connection p.58
- A m l i h g b c f e d p.58
- 2 3 4 5 6 7 8 p.58
- 2 3 4 5 6 7 8 p.59
- Pagina 59 di 67 p.59
- Legend p.59
- Dimensional drawing p.59
- Compressor evaporator condenser coil electrical panel fan evaporator water inlet evaporator water outlet slot for power and control panel connection p.59
- A m l i h g b c f e d p.59
- Pagina 60 di 67 p.60
- Legend p.60
- Dimensional drawing p.60
- Compressor evaporator condenser coil electrical panel fan evaporator water inlet evaporator water outlet slot for power and control panel connection p.60
- A m l i h g b c f e d p.60
- 2 3 4 5 6 7 8 p.60
- Space requirements p.61
- Pagina 61 di 67 p.61
- Location p.61
- Installation notes p.61
- Handling p.61
- Warning p.61
- Installation notes p.62
- Pagina 63 di 67 p.63
- Installation notes p.63
- Unit description p.64
- Technical specifications p.64
- Sound level and vibrations p.64
- Refrigerant p.64
- Performance p.64
- Pagina 64 di 67 p.64
- General p.64
- Evaporator phe p.64
- Dimensions p.64
- Condenser coil p.64
- Controller p.65
- Condenser fans p.65
- Condensation control p.65
- Technical specifications p.65
- Refrigerant circuit p.65
- Pagina 65 di 67 p.65
- Low sound unit configurations on request p.65
- Hydronic kit options on request p.65
- Electrical control panel p.65
- Technical specifications p.66
- Controller main features p.66
- Pagina 66 di 67 p.66
- High level communications interface on request p.66
Похожие устройства
-
Daikin EKHBRD016ADY17Инструкция по монтажу -
Daikin EKHBRD016ADY17Инструкция по эксплуатации -
Daikin EKHBRD014ADY17Инструкция по монтажу -
Daikin EKHBRD014ADY17Инструкция по эксплуатации -
Daikin EKHBRD011ADY17Инструкция по монтажу -
Daikin EKHBRD011ADY17Инструкция по эксплуатации -
Daikin EKHBRD016ADV17Инструкция по монтажу -
Daikin EKHBRD016ADV17Инструкция по эксплуатации -
Daikin EKHBRD014ADV17Инструкция по монтажу -
Daikin EKHBRD014ADV17Инструкция по эксплуатации -
Daikin EKHBRD011ADV17Инструкция по монтажу -
Daikin EKHBRD011ADV17Инструкция по эксплуатации