ELECTRICAL SPECIFICATIONS
EWAQ F-SS
230 250 280 320 350 360 400 210 MODEL
POWER SUPPLY
Phases Nr 3 3 3 3 3 3 3 3
Frequency
Hz
50
50
50
50
50
50
Voltage V 400 400 400 400 400 400 400 400
Voltage tolerance Minimum % -10% -10% -10% -10% -10% -10% -10% -10%
Voltage tolerance Maximum
%
+10%
+10%
+10%
+10%
+10%
+10%
UNIT
Maximum starting current A 349 404 419 476 505 621 649 621
Nominal running current cooling
A
130
147
161
187
208
262
Mximum running current
A
160
176
191
225
254
314
Maximum current for wires sizing A 176 193 210 247 279 314 345 314
FANS
Nominal running current cooling
A
16
16
16
20
20
24
COMPRESSORS
Phases Nr 3 3 3 3 3 3 3 3
Voltage V 400 400 400 400 400 400 400 400
Voltage tolerance Minimum
%
-10%
-10%
-10%
-10%
-10%
-10%
Voltage tolerance Maximum % +10% +10% +10% +10% +10% +10% +10% +10%
Maximum running current
A
72
72
80
80
88
88
102
102
117
117
131
145
145
131
Starting method --- DOL DOL DOL DOL DOL DOL DOL DOL
EWAQ F-SS
480
550
610
410
MODEL
POWER SUPPLY
Phases
Nr
3
3
3
3
Frequency
Hz
50
50
50
50
Voltage V 400 400 400 400
Voltage tolerance Minimum
%
-10%
-10%
-10%
-10%
Voltage tolerance Maximum % +10% +10% +10% +10%
UNIT
Maximum starting current A 649 634 768 810
Nominal running current cooling
A
262
322
356
391
Mximum running current A 314 383 433 474
Maximum current for wires sizing
A
345
421
476
522
FANS
Nominal running current cooling
A
24
32
40
40
COMPRESSORS
Phases Nr 3 3 3 3
Voltage
V
400
400
400
400
Voltage tolerance Minimum % -10% -10% -10% -10%
Voltage tolerance Maximum % +10% +10% +10% +10%
Maximum running current A
145
145
175
175
189
203
217
217
Starting method --- DOL DOL DOL DOL
Fluid: Water
Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
Maximum starting current: starting current of biggest compressor + current of the other compressors at maximum load + fans current at maximum load
Nominal current in cooling mode is referred to the following conditions: evaporator 12/7°C; ambient 35°C; compressors + fans current.
Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current
Maximum unit current for wires sizing is based on minimum allowed voltage
Maximum current for wires sizing: (compressors full load ampere + fans current) x 1,1.