Daikin EWAQ320F-XL [11/67] Ewaq f sl

Daikin EWAQ250F-SS [11/67] Ewaq f sl
TECHNICAL SPECIFICATIONS
EWAQ F-SL
480
550
610
410
MODEL
Capacity - Cooling (1) kW 609 480 407 551
Capacity control - Type
---
Step
Step
Step
Step
Capacity control - Minimum capacity % 17.0 17.0 25.0 14.0
Unit power input - Cooling (1)
kW
229
187
154
207
EER (1)
---
2.66
2.57
2.64
2.67
ESEER --- 3.99 4.10 4.01 4.00
IPLV
---
4.61
4.52
4.42
4.56
CASING
Colour (2)
---
IW
IW
IW
IW
Material (2) --- GPSS GPSS GPSS GPSS
DIMENSIONS
Height
mm
2221
2221
2397
2221
Width mm 2258 2258 2258 2258
Length
mm
5010
4110
3210
5010
WEIGHT
Unit Weight
kg
3912
3315
3068
3679
Operating Weight kg 3958 3362 3108 3725
WATER HEAT EXCHANGER
Type (3)
---
PHE
PHE
PHE
PHE
Water Volume l 46 46 40 46
Nominal water flow rate - Cooling
l/s
29.2
23.0
19.5
26.4
Nominal Water pressure drop - Cooling kPa 56 35 32 46
Insulation material (4)
CC
CC
CC
CC
AIR HEAT EXCHANGER
Type (5) --- HFP HFP HFP HFP
FAN
Type (6) --- DPT DPT DPT DPT
Drive (7)
---
DOL
DOL
DOL
DOL
Diameter mm 800 800 800 800
Nominal air flow
l/s
52870
43690
32513
54612
Quantity
No.
10
8
6
10
Speed rpm 900 900 900 900
Motor input
kW
17.5
14.0
10.5
17.5
COMPRESSOR
Type
---
Scroll
Scroll
Scroll
Scroll
Oil charge l 38 38 25 38
Quantity No. 6 6 4 6
SOUND LEVEL
Sound Power - Cooling dB(A) 96 95 94 96
Sound Pressure - Cooling (8)
dB(A)
76
75
75
76
REFRIGERANT CIRCUIT
Refrigerant type
---
R410A
R410A
R410A
R410A
Refrigerant charge kg 46 34 24 40
N. of circuits No. 2 2 2 2
PIPING CONNECTIONS
Evaporator water inlet/outlet 3" 3" 3" 3"
Fluid: Water
(1) Cooling capacity, unit power input in cooling and EER are based on the following conditions: evaporator 12.0/7.0°C; ambient 35.0°C, unit at full load
operation;
(2) IW: Ivory White; GPSS: Galvanized and Painted Steel Sheet; (3) PHE: Plate Heat Exchanger --- S&T: Single Pass Shell & Tube
(4) CC: Closed Cell; (5) HFP: High efficiency fin and tube type with integral subcooler
(6) DPT: Direct Propeller Type; (7) DOL: Direct On Line - VFD: Inverter - BRS: Brushless
(8) The values are according to ISO 3744 and are referred to: evaporator 12/7°C, ambient 35°C, full load operation.
Pagina 11 di 67

Содержание

Скачать