Daikin EUW12KZW [10/49] Specifications

Daikin EUW10KZW [10/49] Specifications
NOMINAL CAPACITY, CAPACITY STEPS and NOMINAL INPUT
UNITS 60hp 64hp 68hp 72hp
NOMINAL CAPACITY Cooling kW 168 177 186 195
CAPACITY STEPS 6666
NOMINAL INPUT Cooling kW 48.0 50.3 52.6 54.9
EER 3.50 3.52 3.54 3.55
TECHNICAL SPECIFICATIONS
UNITS 60hp 64hp 68hp 72hp
DIMENSIONS Unit H mm 1,800 1,800
W mm 600 600
D mm 1,200 1,200
WEIGHT Machine weight kg 960 974 988 1,002
MATERIAL Polyester painted steel plate
COLOUR Ivory white / Munsell code 5Y7.5/1
SOUND LEVEL Sound pressure dBA −−−−
Sound power dBA 73 76 78 79
EVAPORATOR Type Brased plate heat exchanger
Qty 3333
Minimum water volume in the system l 268 268 268 311
Nominal water flow l/min 482 507 533 559
Water flow range (min/max) l/min 241/963 254/1,015 267/1,066 280/1,118
Insulation material Polyethylene foam
CONDENSER Type Brased plate heat exchanger
Qty 3333
Nominal water flow l/min 614 647 679 711
Water flow range (min/max) l/min 307/1,229 323/1,293 339/1,357 355/1,422
REFRIGERANT CIRCUIT Refrigerant type R-407C
Refrigerant charge kg 13.8 14.8 15.8 16.8
No. of circuits 6666
Refrigerant control Thermostatic expansion valve
COMPRESSOR Type Hermetically sealed scroll
Qty x model 6xJT300DA-YE 4xJT300DA-YE
2xJT335DA-YE
4xJT335DA-YE
2xJT300DA-YE
6xJT335DA-YE
No. of compressors 6666
Speed rpm 2,900 2,900 2,900 2,900
Refrigerant oil type FVC68D
Refrigerant oil charge l 6 x 2.7 6 x 2.7 6 x 2.7 6 x 2.7
PIPING CONNECTIONS Evap. water in/outlet mm 3x2xFBSP 38
Condenser water in/outlet mm 3x2xFBSP 38
Evaporator water drain Field installation
Relief device outlet Field installation
Filter strainer Field installation
Flow switch Field installation
SAFETY DEVICES High pressure switch / Low pressure switch / Freeze-up protection / Reverse phase protector / Discharge temperature protection /
Compressor motor overcurrent / Anti recycling timer / Guard timer
Water-cooled R-407C EUW5-24KZW
3
Specifications
1
3
8