Daikin EUW12KZW [11/49] Specifications

Daikin EUW10KZW [11/49] Specifications
ELECTRICAL SPECIFICATIONS
UNITS EUW5KZW EUW8KZW EUW10KZW EUW12KZW EUW16KZW
POWER SUPPLY W1 W1 W1 W1 W1
NOMINAL DISTRIBUTION
SYSTEM VOLTAGE
Phase 3N 3N 3N 3N 3N
Frequency Hz 50 50 50 50 50
Voltage V 400 400 400 400 400
Voltage tolerance % ± 10 ± 10 ± 10 ± 10 ± 10
UNIT Starting current A 49 79 109 129 93
Nominal running current A 6.6 10.4 13.1 15.0 20.8
Maximum running current A 8 14 18 20 28
Recommended fuses according to IEC
standard 269-2
aM 3x16 3x20 3x25 3x25 3x35
COMPRESSOR Phase 3 3 3 3 3
Frequency Hz 50 50 50 50 50
Voltage V 400 400 400 400 400
Starting current A 49 79 109 129 79
Nominal running current A 6.6 10.4 13.1 15.0 10.4
Maximum running current A 8 14 18 20 14
Starting method Direct on line
ELECTRICAL SPECIFICATIONS
UNITS EUW20KZW EUW24KZW 32hp 36hp 40hp
POWER SUPPLY W1 W1 W1 W1 W1
NOMINAL DISTRIBUTION
SYSTEM VOLTAGE
Phase 3N 3N 3N 3N 3N
Frequency Hz 50 50 50 50 50
Voltage V 400 400 400 400 400
Voltage tolerance % ± 10 ± 10 ± 10 ± 10 ± 10
UNIT Starting current A 127 149 121 155 163
Nominal running current A 26.2 30 41.6 47 52.4
Maximum running current A 36 40 56 64 72
Recommended fuses according to IEC
standard 269-2
aM 3x40 3x50 3x63 3x63 3x80
COMPRESSOR Phase 3 3 3 3 3
Voltage V 400 400 400 400 400
Starting current A 109 129 79 79/109 109
Nominal running current A 13.1 15.0 10.4 10.4/13.1 13.1
Maximum running current A 18 20 14 14/18 18
Starting method Direct on line
Water-cooled R-407C EUW5-24KZW
3
Specifications
1
3
9
Applied Systems Chillers
Скачать