ELECTRICAL SPECIFICATIONS
EWAD TZ-XS
220
265
290
330
360
410
180
MODEL
POWER SUPPLY
Phases
Nr
3
3
3
3
3
3
3
Frequency
Hz
50
50
50
50
50
50
50
Voltage
V
400
400
400
400
400
400
400
Voltage tolerance Minimum
%
-10%
-10%
-10%
-10%
-10%
-10%
-10%
Voltage tolerance Maximum
%
+10%
+10%
+10%
+10%
+10%
+10%
+10%
UNIT
Maximum starting current
A
3
3
3
3
3
3
3
Nominal running current cooling
A
98
118
144
153
182
194
220
Maximum running current
A
124
146
174
190
225
239
267
Maximum current for wires sizing
A
135
160
189
192
246
255
293
FANS
Nominal running current cooling
A
10
13
13
16
21
21
21
COMPRESSORS
Phases
Nr
3
3
3
3
3
3
3
Voltage
V
400
400
400
400
400
400
400
Voltage tolerance Minimum
%
-10%
-10%
-10%
-10%
-10%
-10%
-10%
Voltage tolerance Maximum
%
+10%
+10%
+10%
+10%
+10%
+10%
+10%
Maximum running current
A
113
133
161
174
204
218
123
123
Starting method
---
INV
INV
INV
INV
INV
INV
INV
EWAD TZ-XS
490
540
580
630
690
440
MODEL
POWER SUPPLY
Phases
Nr
3
3
3
3
3
3
Frequency
Hz
50
50
50
50
50
50
Voltage
V
400
400
400
400
400
400
Voltage tolerance Minimum
%
-10%
-10%
-10%
-10%
-10%
-10%
Voltage tolerance Maximum
%
+10%
+10%
+10%
+10%
+10%
+10%
UNIT
Maximum starting current
A
3
3
3
3
3
3
Nominal running current cooling
A
239
267
289
315
344
368
Maximum running current
A
292
321
347
379
411
444
Maximum current for wires sizing
A
320
352
378
383
451
487
FANS
Nominal running current cooling
A
26
26
26
31
31
36
COMPRESSORS
Phases
Nr
3
3
3
3
3
3
Voltage
V
400
400
400
400
400
400
Voltage tolerance Minimum
%
-10%
-10%
-10%
-10%
-10%
-10%
Voltage tolerance Maximum
%
+10%
+10%
+10%
+10%
+10%
+10%
Maximum running current
A
133
133
148
148
161
161
174
174
190
190
204
204
Starting method
---
INV
INV
INV
INV
INV
INV
Fluid: Water
Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
Maximum starting current: Unit is inverter driven. No inrush current at start up. Declared value refers to the stand-by current.
Nominal current in cooling mode is referred to the following conditions: evaporator 12/7°C; ambient 35°C; compressors + fans current.
Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current
Maximum unit current for wires sizing is based on minimum allowed voltage
Maximum current for wires sizing: (compressors full load ampere + fans current) x 1,1.
Page 25 of 75