Daikin EWAD270TZ-PR [27/75] Electrical specifications

Daikin EWAD270TZ-PR [27/75] Electrical specifications
ELECTRICAL SPECIFICATIONS
EWAD TZ-PS
225
250
270
295
320
380
190
MODEL
POWER SUPPLY
Phases
Nr
3
3
3
3
3
3
3
Frequency
Hz
50
50
50
50
50
50
50
Voltage
V
400
400
400
400
400
400
400
Voltage tolerance Minimum
%
-10%
-10%
-10%
-10%
-10%
-10%
-10%
Voltage tolerance Maximum
%
+10%
+10%
+10%
+10%
+10%
+10%
+10%
UNIT
Maximum starting current
A
3
3
3
3
3
3
3
Nominal running current cooling
A
88
107
115
127
139
156
182
Maximum running current
A
117
137
152
165
179
195
232
Maximum current for wires sizing
A
128
151
168
181
181
215
255
FANS
Nominal running current cooling
A
3
3
5
5
5
5
6
COMPRESSORS
Phases
Nr
3
3
3
3
3
3
3
Voltage
V
400
400
400
400
400
400
400
Voltage tolerance Minimum
%
-10%
-10%
-10%
-10%
-10%
-10%
-10%
Voltage tolerance Maximum
%
+10%
+10%
+10%
+10%
+10%
+10%
+10%
Maximum running current
A
113
133
148
161
174
190
113
113
Starting method
---
INV
INV
INV
INV
INV
INV
INV
EWAD TZ-PS
460
505
560
600
645
415
MODEL
POWER SUPPLY
Phases
Nr
3
3
3
3
3
3
Frequency
Hz
50
50
50
50
50
50
Voltage
V
400
400
400
400
400
400
Voltage tolerance Minimum
%
-10%
-10%
-10%
-10%
-10%
-10%
Voltage tolerance Maximum
%
+10%
+10%
+10%
+10%
+10%
+10%
UNIT
Maximum starting current
A
3
3
3
3
3
3
Nominal running current cooling
A
204
219
242
274
295
327
Maximum running current
A
252
273
302
328
356
388
Maximum current for wires sizing
A
278
301
333
359
360
428
FANS
Nominal running current cooling
A
6
7
7
7
8
8
COMPRESSORS
Phases
Nr
3
3
3
3
3
3
Voltage
V
400
400
400
400
400
400
Voltage tolerance Minimum
%
-10%
-10%
-10%
-10%
-10%
-10%
Voltage tolerance Maximum
%
+10%
+10%
+10%
+10%
+10%
+10%
Maximum running current
A
123
123
133
133
148
148
161
161
174
174
190
190
Starting method
---
INV
INV
INV
INV
INV
INV
Fluid: Water
Allowed voltage tolerance ± 10%. Voltage unbalance between phases must be within ± 3%.
Maximum starting current: Unit is inverter driven. No inrush current at start up. Declared value refers to the stand-by current.
Nominal current in cooling mode is referred to the following conditions: evaporator 12/7°C; ambient 35°C; compressors + fans current.
Maximum running current is based on max compressor absorbed current in its envelope and max fans absorbed current
Maximum unit current for wires sizing is based on minimum allowed voltage
Maximum current for wires sizing: (compressors full load ampere + fans current) x 1,1.
Page 27 of 75