MEAN WELL RPT-65F-C [80/112] Rack power

MEAN WELL PS-05-15 [80/112] Rack power
77
19" Rack Power
1000~24000W Distributed Power
• Universal AC input / Full range
• Withstand 300VAC surge for 5 seconds (RCP-1600)
• Built-in active PFC function
• Built-in auxiliary power
• Protections: Short circuit / Overload / Over voltage / Over temperature
• Forced air cooling by built-in DC fan
• High power density up to 25W/inch
3
(RCP-1600)
• 1U low profile (41mm height)
• Output voltage programmable;
Constant current level
Icc programmable (RCP-1600)
Model No. Output Tol. R&N Effi.
RCP-1000-12 12V, 0~60A ±1% 150mV 81.0%
RCP-1000-24 24V, 0~40A ±1% 200mV 87.0%
RCP-1000-48 48V, 0~21A ±1% 300mV 89.0%
Model No. Output Tol. R&N Effi.
RCP-1600-12 12V, 0~125A ±1% 150mV 88.5%
RCP-1600-24 24V, 0~67A ±1% 200mV 91.0%
RCP-1600-48 48V, 0~33.5A ±1% 300mV 93.0%
RCP-1000 RCP-1600 RHP-1URCP-1U
Rectifier: RCP-1000- 12 - C
Rectifier: RCP-1600- 12 - C
Rack Shelf: RCP-1U
I
Rack Shelf: RHP-1U
I -A
C : with I
2
C interface
: without I
2
C interface
Output voltage(12V/24V/48V)
Output voltage(12V/24V/48V)
Features
Order Information for RCP-1000 and RCP-1U
Order Information for RCP-1600 and RHP-1U
General Specification (Please refer to www.meanwell.com for detail spec.)
Order No. RCP-1000 RCP-1600
AC input voltage range 90~264VAC, 127~370VDC
AC inrush current (max.) Cold start, 50A at 230VAC Cold start, 35A at 230VAC
DC adjustment range
Vo: ±3% by potentiometer, or to 90%~110% of rated output
voltage by
external resistor
Vo: -1%~+22.5% by potentiometer, or to 40%~125% of
rated output voltage by 1~5VDC
external control signal
Icc : to 20%~100% of rated output current by 1~5VDC
external control signal
Overload protection (OLP) 105%~125% constant current limiting, auto-recovery
105%~115% constant current limiting, shut down o/p
voltage after 5 sec., re-power on to recover
Over voltage protection 110%~135% shut down o/p voltage, re-power on to recover 130%~155% shut down o/p voltage, re-power on to recover
Withstand voltage I/P-O/P:3kVAC, I/P-FG:2kVAC, O/P-F/G: 0.7kVDC I/P-O/P:3kVAC, I/P-FG:2kVAC, O/P-F/G: 1.5kVAC
Working temperature -20~+60°C (refer to output derating curve) -30~+70°C (refer to output derating curve)
Safety standards UL60950-1, TUV EN60950-1 approved
EMC standards
EN55032 class B (Radiation class A for RCP-1600), EN61000-3-2,3, EN61000-4-2,3,4,5,6,8,11,
EN61000-6-2 heavy industry level
Connection Postronic PCIB24W9M400A1 Postronic PCIM34W13M400A1
Dimension(LxWxH) 295x 127x 41mm (483.6x 350.8x 44mm for RCP-1U) 300x 85x 41mm (440x 365x 44mm for RHP-1U)
Case No. 952A (959A for RCP-1U) 237A (242A for RHP-1U)
Packing
1.93kg (RCP-1000, single unit);
3.9kg (RCP-1U, single empty rack)
1.87kg (RCP-1600, single unit);
5.5kg (RHP-1U, single empty rack)
Active current sharing up to 3 units (RCP-1000) or
5 units (RCP-1600) in one 19" rack, 3 racks max. can be operated
in parallel (up to 8 units for RCP-1000 or 15 units for RCP-1600)
Built-in remote ON/OFF control
Built-in remote sense function
AC OK (RCP-1000) and DC OK signal output
Internal OR-ing diode (RCP-1000) or OR-ing FET (RCP-1600),
hot-swap operation
• Optional I
2
C serial data bus (RCP-1000);
Built-in PMBus serial communication, optional CANBus (RCP-1600)
5 years warranty
I : AC inlet(IEC320-C14)
T : Terminal block
I : AC inlet(IEC320-C14)
T : Terminal block
: Standard model, PMBus protocol
C : Optional model, CANBus protocol
5HFWLILHUŇ:
5HFWLILHUŇ:
For RCP/RCB-1600