Daikin EWWH480DZXEA1 [19/47] Alarms

Daikin EWWH950DZXSA3 [19/47] Alarms
EWWD_DZ EWWH_DZ
D-EOMWC01405-18EN
19/47
Setpoint/Sub-Menu
Default
Range
Description
Unit
Enable
Enable, Disable, Scheduler
Unit enable command
Compressor #1
Enable
Enable, Disable, Test
Compressor #1 enable command
Compressor #2
Enable
Enable, Disable, Test
Compressor #2 enable command
Compressor #3
Enable
Enable, Disable, Test
Compressor #3 enable command
4.9 Timers
This page indicates the remaining cycle timers for each circuit and the remaining staging timers. When the cycle timers
are active any new start of a compressor is inhibited.
Default
Range
Description
0s
-
Compressor 1 cycle timer
0s
-
Compressor 2 cycle timer
0s
-
Compressor 3 cycle timer
Off
Off, On
Clear compressor 1 cycle timer
Off
Off, On
Clear compressor 2 cycle timer
Off
Off, On
Clear compressor 3 cycle timer
0s
-
Remaining delay to next compressor start
0s
-
Remaining delay to next compressor stop
Off
Off, On
Clear remaining delays to next compressor start/stop
0min
-
Remaining Ice cycle delay
Off
Off, On
Clear remaining delay for Ice mode
4.10 Alarms
This link jumps to the same page accessible with the Bell button. Each of the items represents a link to a page with different
information. The information shown depends on the abnormal operating condition that caused the activation of unit, circuit
or compressor safeties. A detailed description of the alarms and how to handle will be discussed in the section 6.
Setpoint/Sub-Menu
Default
Description
Alarm Active
List of the active alarms
Alarm Log
History of all the alarms and acknowledges
Event Log
List of the events
Alarm Snapshot
List of alarm snapshots with all the relevant data recorded at time the alarm occurred.
4.11 Commission Unit
Setpoint/Sub-Menu
Default
Range
Description
Alarms Limits
-
Submenu for alarm limits definition
Calibrate Sensors
-
Submenus for Unit and Circuit sensor calibration
Manual Control
-
Submenus for Unit and Circuit manual control
Scheduled Maintenance
-
Submenu for scheduled maintenance
4.11.1 Alarm Limits
This page contains all alarm limits, including low pressure alarm prevention thresholds. In order to ensure proper operation
they have to be set manually according to the specific application.
Setpoint/Sub-Menu
Default
Range
Description
Low Press Hold=
200.0kPa
0…310.0 kPa
Low pressure safety limit to stop capacity increase (R134a)
Low Press Unld=
190.0kPa
0…250.0 kPa
Low pressure alarm prevention (R134a)
Low Press Hold=
122.0kPa
-27.0…204.0
kPa
Low pressure safety limit to stop capacity increase (VZ with
R1234ze)
Low Press Unld=
114.0kPa
-27.0…159.0
kPa
Low pressure alarm prevention (VZ with R1234ze)
Low Press Hold=
NA
-27.0… 310.0
Low pressure safety limit to stop capacity increase (TZ with
R1234ze)
Low Press Unld=
NA
-27.0… 310.0
Low pressure alarm prevention (TZ with R1234ze)
Hi Oil Pr Dly=
30s
10…180s
Delay for the High oil pressure difference alarm
Hi Oil Pr Diff=
250kPa
0.0…415.0kPa
Pressure drop for a clogged filter
Hi Disch Temp=
110.0°C
Maximum discharge temperature limit
Hi Cond Pr Dly=
5s
Delay on the High pressure alarm from transducer
Lo Pr Ratio Dly=
90s
Delay on the low pressure ratio alarm
OAT Lockout=
4.0°C
Air temperature operational limit
Strt Time Lim=
N/A
Time limit for the low ambient start
Evap Flw Proof=
N/A
Flow proof delay
Evp Rec Timeout=
N/A
Recirculating timeout before the alarm is raised
Evap Water Frz=
2.2°C
-18.0…6.0 °C
Freeze protection limit
Water Flw Proof=
15s
5…15s
Flow proof delay
Water Rec Timeout=
3min
1…10min
Recirculating timeout before the alarm is raised
Low DSH Limit=
12.0°C
Minimum acceptable discharge superheat
Gas Conc Lim=
200ppm
Maximum gas concentration limit